⚡ Mcor Power Quality
Kwadukuza Municipality
Logged in as Corrie Logout

Meter Live History

← Meters📈 Live Values📊 History📅 Schedule📡 Read Log💰 Totals✎ Edit📡 Reader📈 Live History
Meter 10266143 · KZN-VK-Phoenix-Plaza MV Gen · · DB range 2026-11-20 00:00:00 to 2026-11-20 11:48:16 · rendered 63 samples
Latest DB Window
👇 drag across any graph to zoom into that time band (all graphs follow)
Available in DB for this meter: 2026-05-06 20:20:00 to 2026-11-20 10:10:00

1. Live Electrical Snapshot

metcom-module-read-instant-v1
4 graph cards with data

Voltage L1 / L2 / L3 (line)

L1 11.101L3 11.142
11.1011.1111.1211.1311.14 2026-11-19 16:292026-11-20 05:002026-11-20 10:10
ValueLatestUnit
L111.1kV
L311.14kV

Current L1 / L2 / L3

L1 0.200L2 0.000L3 0.200
0.000.050.100.150.20 2026-11-19 16:292026-11-20 05:002026-11-20 10:10
ValueLatestUnit
L10.2A
L20A
L30.2A

Frequency

Hz 50.090
49.0949.5950.0950.5951.09 2026-11-19 16:292026-11-20 05:002026-11-20 10:10
ValueLatestUnit
Hz50.09Hz

Total PF

PF -0.540
-1.54-1.04-0.54-0.040.46 2026-11-19 16:292026-11-20 05:002026-11-20 10:10
ValueLatestUnit
PF-0.54

2. IEC Live / Energy / Power Detail

limo-metcom-v1
2 graph cards with data

Total kW / kVA / kvar

kW 2.560
1.562.062.563.063.56 2026-11-19 16:292026-11-20 05:002026-11-20 10:10
ValueLatestUnit
kW2.56

Phasor Angles

81.7.4 -103.70081.7.15 27.30081.7.26 173.000
-103.70-34.5334.65103.82173.00 2026-11-19 16:292026-11-20 05:002026-11-20 10:10
ValueLatestUnit
81.7.4-103.7deg
81.7.1527.3deg
81.7.26173deg

4. P.06 Interval PQ — NRS compliance inputs (voltage / frequency / unbalance)

metcom_profile6_value_rows
3 graph cards with data

P.06 Voltage L1 / L2 / L3 (interval, kV primary)

L1 11314.000L2 0.000L3 11404.000
0.002872.255744.508616.7511489.00 2026-11-20 00:002026-11-20 05:102026-11-20 10:10
ValueLatestUnit
L11.131e+04kV
L20kV
L31.14e+04kV

P.06 Frequency (interval)

Hz 49.970
49.7649.8649.9550.0550.15 2026-11-20 00:002026-11-20 05:102026-11-20 10:10
ValueLatestUnit
Hz49.97Hz

P.06 Voltage Unbalance (NEMA, from phases)

Unbalance 100.000
99.0099.50100.00100.50101.00 2026-11-20 00:002026-11-20 05:102026-11-20 10:10
ValueLatestUnit
Unbalance100%

5. THD (from P.06 profile)

metcom_profile6_value_rows
1 graph cards with data

P6 Voltage THD L1 / L2 / L3

L1 1.300L2 0.000L3 1.300
0.000.350.701.051.40 2026-11-19 16:292026-11-20 05:002026-11-20 10:10
ValueLatestUnit
L11.3%
L20%
L31.3%

6. Harmonics

metcom_profile6_value_rows
3 graph cards with data

P6 Voltage Harmonics L1

H3 0.500H5 0.800H7 0.700
0.500.620.750.881.00 2026-11-19 16:292026-11-20 05:002026-11-20 10:10
ValueLatestUnit
H30.5%
H50.8%
H70.7%

P6 Voltage Harmonics L2

H3 0.000H5 0.000H7 0.000
-1.00-0.500.000.501.00 2026-11-19 16:292026-11-20 05:002026-11-20 10:10
ValueLatestUnit
H30%
H50%
H70%

P6 Voltage Harmonics L3

H3 0.300H5 0.900H7 0.700
0.200.400.600.801.00 2026-11-19 16:292026-11-20 05:002026-11-20 10:10
ValueLatestUnit
H30.3%
H50.9%
H70.7%