Meter Live History
← Meters📈 Live Values📊 History📅 Schedule📡 Read Log💰 Totals✎ Edit📡 Reader📈 Live History
Meter 10266105
· Stanger-Sappi Feed 2 (33KV)
·
· DB range 2026-07-23 00:00:00 to 2026-07-23 01:39:43
· rendered 14 samples
👇 drag across any graph to zoom into that time band (all graphs follow)
Available in DB for this meter: 2026-04-04 04:00:00 to 2026-07-23 01:37:48
1. Live Electrical Snapshot
metcom-module-read-instant-v1
4
graph cards with data
Voltage L1 / L2 / L3 (line)
L1 34.035L2 34.383L3 34.373
| Value | Latest | Unit |
| L1 | 34.03 | kV |
| L2 | 34.38 | kV |
| L3 | 34.37 | kV |
Current L1 / L2 / L3
L1 142.500L2 152.500L3 143.000
| Value | Latest | Unit |
| L1 | 142.5 | A |
| L2 | 152.5 | A |
| L3 | 143 | A |
Frequency
Hz 50.010
| Value | Latest | Unit |
| Hz | 50.01 | Hz |
Total PF
PF 0.977
2. IEC Live / Energy / Power Detail
limo-metcom-v1
2
graph cards with data
Total kW / kVA / kvar
kW 8485500.000
| Value | Latest | Unit |
| kW | 8.486e+06 | |
Phasor Angles
81.7.4 9.10081.7.15 12.00081.7.26 13.500
| Value | Latest | Unit |
| 81.7.4 | 9.1 | deg |
| 81.7.15 | 12 | deg |
| 81.7.26 | 13.5 | deg |
4. P.06 Interval PQ — NRS compliance inputs (voltage / frequency / unbalance)
metcom_profile6_value_rows
3
graph cards with data
P.06 Voltage L1 / L2 / L3 (interval, kV primary)
L1 19.638L2 19.836L3 19.827
| Value | Latest | Unit |
| L1 | 19.64 | kV |
| L2 | 19.84 | kV |
| L3 | 19.83 | kV |
P.06 Frequency (interval)
Hz 50.070
| Value | Latest | Unit |
| Hz | 50.07 | Hz |
P.06 Voltage Unbalance (NEMA, from phases)
Unbalance 0.653
| Value | Latest | Unit |
| Unbalance | 0.653 | % |
5. THD (from P.06 profile)
metcom_profile6_value_rows
1
graph cards with data
P6 Voltage THD L1 / L2 / L3
L1 0.500L2 0.900L3 0.600
| Value | Latest | Unit |
| L1 | 0.5 | % |
| L2 | 0.9 | % |
| L3 | 0.6 | % |
6. Harmonics
metcom_profile6_value_rows
3
graph cards with data
P6 Voltage Harmonics L1
H3 0.200H5 0.300H7 0.300
| Value | Latest | Unit |
| H3 | 0.2 | % |
| H5 | 0.3 | % |
| H7 | 0.3 | % |
P6 Voltage Harmonics L2
H3 0.600H5 0.400H7 0.300
| Value | Latest | Unit |
| H3 | 0.6 | % |
| H5 | 0.4 | % |
| H7 | 0.3 | % |
P6 Voltage Harmonics L3
H3 0.200H5 0.300H7 0.200
| Value | Latest | Unit |
| H3 | 0.2 | % |
| H5 | 0.3 | % |
| H7 | 0.2 | % |