⚡ Mcor Power Quality
Kwadukuza Municipality
Logged in as Corrie Logout

Meter Live History

← Meters📈 Live Values📊 History📅 Schedule📡 Read Log💰 Totals✎ Edit📡 Reader📈 Live History
Meter 10266103 · Stanger-Feeder 1 (33KV) · · DB range 2026-07-23 00:00:00 to 2026-07-23 01:39:42 · rendered 16 samples
Latest DB Window
👇 drag across any graph to zoom into that time band (all graphs follow)
Available in DB for this meter: 2026-04-02 22:40:00 to 2026-07-23 01:34:57

1. Live Electrical Snapshot

metcom-module-read-instant-v1
4 graph cards with data

Voltage L1 / L2 / L3 (line)

L1 34.035L2 34.352L3 34.326
33.8934.0534.2034.3634.51 2026-07-23 00:002026-07-23 00:402026-07-23 01:34
ValueLatestUnit
L134.03kV
L234.35kV
L334.33kV

Current L1 / L2 / L3

L1 42.500L2 45.000L3 42.500
41.0042.2543.5044.7546.00 2026-07-23 00:002026-07-23 00:402026-07-23 01:34
ValueLatestUnit
L142.5A
L245A
L342.5A

Frequency

Hz 50.020
49.9750.0350.0950.1450.20 2026-07-23 00:002026-07-23 00:402026-07-23 01:34
ValueLatestUnit
Hz50.02Hz

Total PF

PF 0.993
0.990.990.990.990.99 2026-07-23 00:002026-07-23 00:402026-07-23 01:34
ValueLatestUnit
PF0.993

2. IEC Live / Energy / Power Detail

limo-metcom-v1
2 graph cards with data

Total kW / kVA / kvar

kW 2593500.000
2535000.002576250.002617500.002658750.002700000.00 2026-07-23 00:002026-07-23 00:402026-07-23 01:34
ValueLatestUnit
kW2.594e+06

Phasor Angles

81.7.4 0.90081.7.15 3.00081.7.26 3.800
0.902.323.755.176.60 2026-07-23 00:002026-07-23 00:402026-07-23 01:34
ValueLatestUnit
81.7.40.9deg
81.7.153deg
81.7.263.8deg

4. P.06 Interval PQ — NRS compliance inputs (voltage / frequency / unbalance)

metcom_profile6_value_rows
3 graph cards with data

P.06 Voltage L1 / L2 / L3 (interval, kV primary)

L1 19.653L2 19.854L3 19.848
19.5819.6519.7219.7919.85 2026-07-23 00:002026-07-23 00:302026-07-23 01:00
ValueLatestUnit
L119.65kV
L219.85kV
L319.85kV

P.06 Frequency (interval)

Hz 50.080
49.9750.0250.0650.1050.15 2026-07-23 00:002026-07-23 00:302026-07-23 01:00
ValueLatestUnit
Hz50.08Hz

P.06 Voltage Unbalance (NEMA, from phases)

Unbalance 0.667
0.640.650.670.680.69 2026-07-23 00:002026-07-23 00:302026-07-23 01:00
ValueLatestUnit
Unbalance0.667%

5. THD (from P.06 profile)

metcom_profile6_value_rows
1 graph cards with data

P6 Voltage THD L1 / L2 / L3

L1 0.500L2 0.900L3 0.600
0.500.600.700.800.90 2026-07-23 00:002026-07-23 00:402026-07-23 01:34
ValueLatestUnit
L10.5%
L20.9%
L30.6%

6. Harmonics

metcom_profile6_value_rows
3 graph cards with data

P6 Voltage Harmonics L1

H3 0.200H5 0.300H7 0.300
0.200.230.250.280.30 2026-07-23 00:002026-07-23 00:402026-07-23 01:34
ValueLatestUnit
H30.2%
H50.3%
H70.3%

P6 Voltage Harmonics L2

H3 0.600H5 0.400H7 0.300
0.300.380.450.520.60 2026-07-23 00:002026-07-23 00:402026-07-23 01:34
ValueLatestUnit
H30.6%
H50.4%
H70.3%

P6 Voltage Harmonics L3

H3 0.200H5 0.400H7 0.200
0.200.250.300.350.40 2026-07-23 00:002026-07-23 00:402026-07-23 01:34
ValueLatestUnit
H30.2%
H50.4%
H70.2%