⚡ PQ Thresholds Comparison

⬇ Excel
Each meter's programmed PQ thresholds & CT/VT setup (from Setup Read), compared against NRS 048-2 / EN 50160 limits and against each other. ● Green = meets NRS limit   Blue text = meets NRS but sits exactly on the limit (a tighter setpoint has more margin)   ● Red = outside NRS limit   ● Amber = differs from the other meters (odd-one-out).
Timer rows (persistence times) are judged against the typical as the preferred midpoint — green cell either way, with green text = at typical, blue text = under (faster), red text = over (slower). The Σ / Check column totals numeric setups (e.g. CT sizes) and flags whether all meters match.
ParameterNRS 048-2 / EN 50160Stanger-Feeder 1 (33KV)Stanger-Feeder 2 (33kV)Stanger-Gelnhills Feed (33KV)Stanger-Groutville Phase1 (33KV)Stanger-Sappi Feed 1 (33KV)Stanger-Sappi Feed 2 (33KV)Shakaskraal-Feeder 1 (North) (33KV)Shakaskraal-Feeder 2 (South) (33KV)Ballito Sub (Feeder 1) (33KV)Zimbali Sub (Feeder 2) (33KV)Σ / Check
General / Nominal
nominal_voltage110 V
nominal_current
Maximum current (Imax)1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A✓ same · Σ 10
nominal_frequency50 Hz
Measurement Period 3 (PQ intervals)600 s600 s · 10 min300 s · 5 min600 s · 10 min600 s · 10 min60 s · 1 min600 s · 10 min300 s · 5 min300 s · 5 min300 s · 5 min300 s · 5 min⚠ differ · Σ 3960 · 60–600
CT / VT Ratios
CT primary500 A400 A400 A800 A500 A500 A1600 A1600 A600 A400 Aindividual
CT secondary1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A✓ same · Σ 10
CT ratio500/1400/1400/1800/1500/1500/11600/11600/1600/1400/1individual
VT primary33000 V33000 V33000 V33000 V33000 V33000 V33000 V33000 V33000 V33000 V✓ same · Σ 330000
VT secondary110 V110 V110 V110 V110 V110 V110 V110 V110 V110 V✓ same · Σ 1100
VT ratio33000/11033000/11033000/11033000/11033000/11033000/11033000/11033000/11033000/11033000/110✓ same
Over Voltage — Swell
Over Voltage swell threshold≥ 110% Vn (≥ 121 V)121 V (110% Vn)121 V (110% Vn)121 V (110% Vn)121 V (110% Vn)121 V (110% Vn)121 V (110% Vn)121 V (110% Vn)121 V (110% Vn)121 V (110% Vn)121 V (110% Vn)✓ same · Σ 1210
Time threshold Over Voltage swell3 s typical3 s1 s3 s3 s0 s0 s1 s1 s1 s1 s⚠ differ · Σ 14 · 0–3
Under Voltage — Sag 1
Under Voltage sag 1 threshold≤ 90% Vn (≤ 99 V)99 V (90% Vn)99 V (90% Vn)99 V (90% Vn)99 V (90% Vn)104 V (94.5% Vn)99 V (90% Vn)99 V (90% Vn)99 V (90% Vn)99 V (90% Vn)99 V (90% Vn)⚠ differ · Σ 995 · 99–104
Time threshold Under Voltage sag 13 s typical3 s1 s3 s3 s0 s0 s1 s1 s1 s1 s⚠ differ · Σ 14 · 0–3
Under Voltage — Sag 2
Under Voltage sag 2 threshold< 1% Vn (< 1.1 V)4 V (3.6% Vn)4 V (3.6% Vn)4 V (3.6% Vn)4 V (3.6% Vn)83 V (75.5% Vn)4 V (3.6% Vn)4 V (3.6% Vn)4 V (3.6% Vn)4 V (3.6% Vn)4 V (3.6% Vn)⚠ differ · Σ 119 · 4–83
Time threshold Under Voltage sag 2≤ 3 min · typ 3 s3 s1 s3 s3 s0 s0 s1 s1 s1 s1 s⚠ differ · Σ 14 · 0–3
Power Failure
Power failure voltage cut threshold< 1% Vn (< 1.1 V)1.8 % (2 V)1.8 % (2 V)1.8 % (2 V)1.8 % (2 V)1.8 % (2 V)1.8 % (2 V)1.8 % (2 V)1.8 % (1.999 V)1.8 % (2 V)1.8 % (2 V)✓ same · Σ 18.1809
Time threshold long power failure> 3 min · typ 3 s3 s1 s3 s3 s0 s0 s1 s1 s1 s1 s⚠ differ · Σ 14 · 0–3
Voltage Limits (W1)
Min. valid voltage (Umin ignore)85% Vn (93.5 V)15 % (→ 93.5 V)15 % (→ 93.5 V)15 % (→ 93.5 V)15 % (→ 93.5 V)8 % (→ 101.2 V)15 % (→ 93.5 V)15 % (→ 93.5 V)15 % (→ 93.5 V)15 % (→ 93.5 V)15 % (→ 93.5 V)⚠ differ · Σ 143 · 8–15
Max. valid voltage (Umax ignore)110% Vn (121 V)15 % (→ 126.5 V)15 % (→ 126.5 V)15 % (→ 126.5 V)15 % (→ 126.5 V)8 % (→ 118.8 V)15 % (→ 126.5 V)15 % (→ 126.5 V)15 % (→ 126.5 V)15 % (→ 126.5 V)15 % (→ 126.5 V)⚠ differ · Σ 143 · 8–15
Low voltage threshold Uunder≥ 85% Vn (≥ 93.5 V)10 % (→ 99 V)10 % (→ 99 V)10 % (→ 99 V)10 % (→ 99 V)10 % (→ 99 V)10 % (→ 99 V)10 % (→ 99 V)10 % (→ 99 V)10 % (→ 99 V)10 % (→ 99 V)✓ same · Σ 100
High voltage threshold Uover≤ 110% Vn (≤ 121 V)10 % (→ 121 V)10 % (→ 121 V)10 % (→ 121 V)10 % (→ 121 V)10 % (→ 121 V)10 % (→ 121 V)10 % (→ 121 V)10 % (→ 121 V)10 % (→ 121 V)10 % (→ 121 V)✓ same · Σ 100
Threshold slow voltage changes (W1)95.0 %95.0 %95.0 %95.0 %95.0 %95.0 %95.0 %95.0 %95.0 %95.0 %✓ same · Σ 950
THD Limits (W2)
Voltage THD limit (W2)≤ 8%8.0 %8.0 %8.0 %8.0 %8.0 %8.0 %8.0 %8.0 %8.0 %8.0 %✓ same · Σ 80
Current THD limit (W2)≤ 8%8.0 %8.0 %8.0 %8.0 %8.0 %8.0 %8.0 %8.0 %8.0 %8.0 %✓ same · Σ 80
Unbalance (W3)
Voltage unbalance limit (W3)≤ 2%2.0 %2.0 %2.0 %2.0 %2.0 %2.0 %2.0 %2.0 %2.0 %2.0 %✓ same · Σ 20
Frequency
Frequency limit±1% (± 0.5 Hz)2 % (± 1 Hz)2 % (± 1 Hz)2 % (± 1 Hz)2 % (± 1 Hz)2 % (± 1 Hz)2 % (± 1 Hz)2 % (± 1 Hz)2 % (± 1 Hz)2 % (± 1 Hz)2 % (± 1 Hz)✓ same · Σ 20
Neutral Wire
Missing neutral wire deviation[8, 12][8, 12][8, 12][8, 12][8, 12][8, 12][8, 12][8, 12][8, 12][8, 12]✓ same
Threshold data read at: Stanger-Feeder 1 (33KV): 2026-06-23 11:29:21 SAST | Stanger-Feeder 2 (33kV): 2026-06-23 11:40:55 SAST | Stanger-Gelnhills Feed (33KV): 2026-06-23 11:41:01 SAST | Stanger-Groutville Phase1 (33KV): 2026-06-23 11:40:56 SAST | Stanger-Sappi Feed 1 (33KV): 2026-06-27 12:46:37 SAST | Stanger-Sappi Feed 2 (33KV): 2026-06-23 11:41:06 SAST | Shakaskraal-Feeder 1 (North) (33KV): 2026-06-23 11:41:12 SAST | Shakaskraal-Feeder 2 (South) (33KV): 2026-06-23 11:40:52 SAST | Ballito Sub (Feeder 1) (33KV): 2026-06-23 11:41:05 SAST | Zimbali Sub (Feeder 2) (33KV): 2026-06-23 11:40:55 SAST

📖 NRS 048-2 / EN 50160 Full Compliance Reference

❶ Continuous Parameter Compliance (95% rule)
ParameterLimitTarget
Voltage magnitudeVn ± 10%≥ 95% of week
Voltage magnitude (abs)Vn +10% / −15%100% of week
THDu (voltage)≤ 8%≥ 95% of week
Voltage unbalance≤ 2% (LV/MV)≥ 95% of week
Frequency (interconnected)± 1%≥ 99.5% of year
Frequency (abs limit)47 – 52 Hz100% of time
Flicker Plt≤ 1.0≥ 95% of week
Assessment: 10-min RMS averages · 7-day rolling window · 1 008 bins per parameter. Exclude zero-voltage (outage) periods before computing percentiles.
❷ Voltage Event Logging (count occurrences)
EventVoltage levelDuration
Voltage Sag (Dip)< 90% Vn10 ms – 1 min
Voltage Swell> 110% Vnany
Short Interruption< 1% Vn< 3 min
Long Interruption< 1% Vn≥ 3 min
P.53 (PQ Log) = sags & swells; stores voltage level at event (Event Param 1).
P.52 (Power Failure Log) = long interruptions; stores duration in seconds.
NRS 048-2 classifies sags by depth × duration (Type X/Y/Z for SA overhead lines).
❸ Data Integrity & Availability Index
Required for NERSA quarterly submission:
• % of valid 10-min measurement intervals captured in the reporting period
• Declare all offline / communication-loss windows
• Minimum acceptable: ≥ 95% data availability per meter per month
• Outage periods (zero voltage) must be flagged separately — not counted as non-compliance
• Load-shedding intervals must be identified and disclosed (compare P.52 timestamps vs Eskom schedule)
⚡ Individual Harmonic Voltage Limits (% of Vn, 95% of week)
OrderLimitOrderLimit
H35.0%H56.0%
H75.0%H91.5%
H113.5%H133.0%
H22.0%H41.0%
H17, H192.0%H6–H240.5%
H23, H251.5%>H250.2+32.5/h %
⚠ Eskom Supply vs Municipality — Distinguishing Issues
Eskom upstream issue indicators:
• Incoming voltage low at incomer meter AND low at all downstream feeders simultaneously
• Frequency out of range at all meters at same time
• Power failure (P.52) timestamp matches Eskom load-shedding schedule

Municipality / local issue indicators:
• Voltage drop on specific feeder only while other feeders normal
• High current draw preceding voltage sag (local overload)
• THD or unbalance violation isolated to one substation
• P.52 timestamp does NOT match Eskom load-shedding schedule

NERSA reporting: NRS 048-2 requires reporting party to clearly distinguish supply-side from network-side non-compliance in quarterly submissions.
📋 Meter Recording Requirements (Metcom MCS301)
Profile P.06 (15-min interval data): Voltage (V), current (A), frequency (Hz), kW, kVAr, kVA, PF, THDu, unbalance — stored per phase per interval.
Profile P.53 (PQ event log): Sags & swells — timestamp, duration, voltage level at event (Event Param 1 = voltage in V). Key for severity classification.
Profile P.52 (Power Failure log): Long interruptions — timestamp + duration (seconds). Read via DLMS ProfileGeneric (OBIS 1-0:99.97.0*255).
Profile P.98 (Standard event log): Programming changes, resets, covers.
Measurement period: Should be 600 s (10 min) for NRS 048-2 compliance. Meters programmed at 300 s (5 min) still comply — data is aggregatable.