✅ NRS 048-2 Compliance

⬇ Excel
Per-substation NERSA compliance verdict. The busbar = the combined feed = Eskom point of supply; a parameter failing at the busbar is an Eskom issue, one failing on a single feeder only is a local network issue. Weekly = 95th-percentile of 10-min values; quarterly = weeks-within-limit.

Week of 21 Sep – 27 Sep 2026

1/3 substations fully compliant
MeterVoltageTHDUnbalanceFrequencyAvailabilityOverall
🏭 Driefontein Substation's — busbar = Eskom point of supply
⏻ Busbar (Eskom supply)100.61–103.49%1.5%okok5% ⚠FAIL
Ballito Sub (Feeder 1) (33KV)100.99–104.27%1.0%okok5% ⚠FAIL
Zimbali Sub (Feeder 2) (33KV)100.47–104.41%2.1%okok5% ⚠FAIL
⚠ Eskom: unbalance
🏭 Shakaskraal Substation — busbar = Eskom point of supply
⏻ Busbar (Eskom supply)101.99–103.69%0.9%okok5% ⚠FAIL
Shakaskraal-Feeder 1 (North) (33KV)101.6–103.43%0.7%okok5% ⚠FAIL
Shakaskraal-Feeder 2 (South) (33KV)102.21–103.81%1.2%okok5% ⚠FAIL
⚠ Eskom: unbalance
🏭 Stanger Substation — busbar = Eskom point of supply
⏻ Busbar (Eskom supply)101.81–105.2%0.93%1.0%ok57% ⚠PASS
Stanger-Feeder 1 (33KV)101.8–105.05%0.9%1.0%ok5% ⚠PASS
Stanger-Feeder 2 (33kV)101.78–105.19%0.84%1.0%ok5% ⚠PASS
Stanger-Gelnhills Feed (33KV)101.77–105.04%0.9%1.0%ok5% ⚠PASS
Stanger-Groutville Phase1 (33KV)99.78–108.16%1.6%3.71%ok5% ⚠FAIL
Stanger-Sappi Feed 1 (33KV)101.8–105.17%0.9%0.97%ok57% ⚠PASS
Stanger-Sappi Feed 2 (33KV)101.81–105.23%0.9%0.96%ok6% ⚠PASS
⚠ Local: unbalance (10266107)
How to read: green = within NRS 048-2 limit, red = breach, grey = no data. Voltage cell = 5th–95th percentile (% of Vn, limit 90–110%); THD ≤ 8%; Unbalance ≤ 2%; Frequency ±1%. Quarterly cells show weeks-within-limit. Availability < 95% (⚠) means the verdict is low-confidence — fill the gaps (catch-up reads) before relying on it for NERSA.