✅ NRS 048-2 Compliance

⬇ Excel
Per-substation NERSA compliance verdict. The busbar = the combined feed = Eskom point of supply; a parameter failing at the busbar is an Eskom issue, one failing on a single feeder only is a local network issue. Weekly = 95th-percentile of 10-min values; quarterly = weeks-within-limit.

Week of 20 Jul – 26 Jul 2026

1/3 substations fully compliant
MeterVoltageTHDUnbalanceFrequencyAvailabilityOverall
🏭 Driefontein Substation's — busbar = Eskom point of supply
⏻ Busbar (Eskom supply)101.48–103.94%1.8%okok41% ⚠FAIL
Ballito Sub (Feeder 1) (33KV)100.75–105.12%1.2%okok41% ⚠FAIL
Zimbali Sub (Feeder 2) (33KV)100.59–104.44%2.6%okok41% ⚠FAIL
⚠ Eskom: unbalance
🏭 Shakaskraal Substation — busbar = Eskom point of supply
⏻ Busbar (Eskom supply)102.07–105.0%1.05%okok41% ⚠FAIL
Shakaskraal-Feeder 1 (North) (33KV)101.67–104.81%0.8%okok41% ⚠FAIL
Shakaskraal-Feeder 2 (South) (33KV)102.31–105.44%1.4%okok41% ⚠FAIL
⚠ Eskom: unbalance
🏭 Stanger Substation — busbar = Eskom point of supply
⏻ Busbar (Eskom supply)102.07–105.5%0.92%1.07%ok100%PASS
Stanger-Feeder 1 (33KV)102.09–105.39%0.9%1.06%ok41% ⚠PASS
Stanger-Feeder 2 (33kV)102.05–105.47%0.9%1.07%ok39% ⚠PASS
Stanger-Gelnhills Feed (33KV)102.07–105.38%0.9%1.06%ok41% ⚠PASS
Stanger-Groutville Phase1 (33KV)99.25–108.62%1.6%4.16%ok41% ⚠FAIL
Stanger-Sappi Feed 1 (33KV)102.05–105.47%0.9%1.05%ok100%PASS
Stanger-Sappi Feed 2 (33KV)102.07–105.37%0.9%1.08%ok41% ⚠PASS
⚠ Local: unbalance (10266107)
How to read: green = within NRS 048-2 limit, red = breach, grey = no data. Voltage cell = 5th–95th percentile (% of Vn, limit 90–110%); THD ≤ 8%; Unbalance ≤ 2%; Frequency ±1%. Quarterly cells show weeks-within-limit. Availability < 95% (⚠) means the verdict is low-confidence — fill the gaps (catch-up reads) before relying on it for NERSA.