⚡ Mcor Power Quality
Kwadukuza Municipality
Logged in as Corrie Logout
MCOR Power Quality
Meter PQ ReportShakaskraal-Feeder 1 (North) (33KV)
Doc No:MCOR-PQ-0006
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-07-23 00:25:21 SAST
Meter Serial: 10266106
Site: Kwadukuza Municipality
Feeder: 7
Area: Shakaskraal Substation
Last Reading: 2026-07-23 00:16
Quarter: Q2 2026

10.3   Voltage Compliance

ParameterNERSA LimitMeasuredStatus
Voltage PQ Events (threshold log)≤ 40 / quarter4016 eventsNon-Compliant
Power Failures / Outages≤ 20 / quarter2552 eventsNon-Compliant
Voltage Unbalance≤ 2%Pending
Flicker Pst (short-term)≤ 1.0Max 0.00Compliant
Flicker Plt (long-term)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitL1L2L3Status
THD Voltage (VTHD)≤ 5% 0.7%0.0%0.7% Compliant
3rd Harmonic (V)Review 0.4%0.0%0.2% Compliant
5th Harmonic (V)≤ 3% 0.3%0.0%0.4% Compliant
7th Harmonic (V)≤ 3% 0.4%0.0%0.4% Compliant

10.5   Loading & Power Factor

ParameterL1L2L3Value
Voltage (V)34230.0V0.0V34275.0VUnbal: —
Current (A)54.400A0.000A49.600A
Active PowerTotal: 2793.600 kWPF: 0.779
Frequency50.130 HzCompliant

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events4016HighDLMS event log codes 210-213
Power Failures / Outages2552HighPower fail log entries
Power Cycle Events2574InvestigateCodes 1 & 2
Harmonic Exceedances (H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
VTHD Compliance≤ 5%0.7%Compliant
Voltage Unbalance≤ 2%Pending
PQ Threshold Events≤ 40 / quarter4016Non-Compliant
Outages≤ 20 / quarter2552Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit