Meter PQ ReportStanger-Sappi Feed 2 (33KV)
Doc No:MCOR-PQ-0008
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-11-20 11:32:17 SAST
Meter Serial: 10266105
Site: Kwadukuza Municipality
Feeder: 6
Area: Stanger Substation
Last Reading: 2026-10-30 15:33
Quarter: Q2 2026

10.3   Voltage Compliance

ParameterNERSA LimitMeasuredStatus
Voltage PQ Events (threshold log)≤ 40 / quarter47032 eventsNon-Compliant
Power Failures / Outages≤ 20 / quarter22917 eventsNon-Compliant
Voltage Unbalance≤ 2%1.26%Compliant
Flicker Pst (short-term)≤ 1.0Max 0.00Compliant
Flicker Plt (long-term)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitL1L2L3Status
THD Voltage (VTHD)≤ 5% 0.7%0.8%0.7% Compliant
3rd Harmonic (V)Review 0.2%0.5%0.2% Compliant
5th Harmonic (V)≤ 3% 0.6%0.5%0.6% Compliant
7th Harmonic (V)≤ 3% 0.1%0.0%0.0% Compliant

10.5   Loading & Power Factor

ParameterL1L2L3Value
Voltage (V)19623.0V19863.0V19872.0VUnbal: 1.26%
Current (A)140.000A152.000A141.000A—
Active PowerTotal: 8302.500 kWPF: 0.978
Frequency49.930 HzCompliant

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events47032HighDLMS event log codes 210-213
Power Failures / Outages22917HighPower fail log entries
Power Cycle Events28148InvestigateCodes 1 & 2
Harmonic Exceedances (H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
VTHD Compliance≤ 5%0.8%Compliant
Voltage Unbalance≤ 2%1.26%Compliant
PQ Threshold Events≤ 40 / quarter47032Non-Compliant
Outages≤ 20 / quarter22917Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit