⚡ Mcor Power Quality
Kwadukuza Municipality
Logged in as Corrie Logout
MCOR Power Quality
Meter PQ ReportStanger-Feeder 2 (33kV)
Doc No:MCOR-PQ-0003
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-09-21 12:04:31 SAST
Meter Serial: 10266104
Site: Kwadukuza Municipality
Feeder: 2
Area: Stanger Substation
Last Reading: 2026-09-21 12:02
Quarter: Q2 2026

10.3   Voltage Compliance

ParameterNERSA LimitMeasuredStatus
Voltage PQ Events (threshold log)≤ 40 / quarter27312 eventsNon-Compliant
Power Failures / Outages≤ 20 / quarter10638 eventsNon-Compliant
Voltage Unbalance≤ 2%2.07%Non-Compliant
Flicker Pst (short-term)≤ 1.0Max 0.00Compliant
Flicker Plt (long-term)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitL1L2L3Status
THD Voltage (VTHD)≤ 5% 0.6%0.8%0.6% Compliant
3rd Harmonic (V)Review 0.1%0.6%0.2% Compliant
5th Harmonic (V)≤ 3% 0.5%0.4%0.4% Compliant
7th Harmonic (V)≤ 3% 0.1%0.1%0.2% Compliant

10.5   Loading & Power Factor

ParameterL1L2L3Value
Voltage (V)19845.0V19710.0V19437.0VUnbal: 2.07%
Current (A)120.400A120.400A116.000A
Active PowerTotal: 6627.600 kWPF: 0.938
Frequency49.950 HzCompliant

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events27312HighDLMS event log codes 210-213
Power Failures / Outages10638HighPower fail log entries
Power Cycle Events8253InvestigateCodes 1 & 2
Harmonic Exceedances (H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
VTHD Compliance≤ 5%0.8%Compliant
Voltage Unbalance≤ 2%2.07%Non-Compliant
PQ Threshold Events≤ 40 / quarter27312Non-Compliant
Outages≤ 20 / quarter10638Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit