| Doc No: | MCOR-PQ-0005 |
| Document Ref: | MCOR-PQ-2026-Q2 |
| Period: | 2026-04-01 to 2026-06-30 |
| Generated | 2026-06-26 11:57:45 SAST |
| Parameter | NERSA Limit | Measured | Status |
|---|---|---|---|
| Voltage PQ Events (threshold log) | ≤ 40 / quarter | 84 events | Non-Compliant |
| Power Failures / Outages | ≤ 20 / quarter | 20 events | Compliant |
| Voltage Unbalance | ≤ 2% | — | Pending |
| Flicker Pst (short-term) | ≤ 1.0 | Max 0.00 | Compliant |
| Flicker Plt (long-term) | ≤ 0.8 | 0.00 | Compliant |
| Parameter | NERSA Limit | L1 | L2 | L3 | Status |
|---|---|---|---|---|---|
| THD Voltage (VTHD) | ≤ 5% | 1.1% | 0.0% | 1.2% | Compliant |
| 3rd Harmonic (V) | Review | 0.5% | 0.0% | 0.5% | Compliant |
| 5th Harmonic (V) | ≤ 3% | 0.6% | 0.0% | 0.6% | Compliant |
| 7th Harmonic (V) | ≤ 3% | 0.7% | 0.0% | 0.7% | Compliant |
| Parameter | L1 | L2 | L3 | Value |
|---|---|---|---|---|
| Voltage (V) | 32592.0V | 0.0V | 33318.0V | Unbal: — |
| Current (A) | 297.000A | 0.000A | 303.600A | — |
| Active Power | Total: 17010.000 kW | PF: 0.861 | ||
| Frequency | 50.110 Hz | Compliant | ||
| Event Type | Count | Severity | Notes |
|---|---|---|---|
| Voltage PQ Threshold Events | 84 | High | DLMS event log codes 210-213 |
| Power Failures / Outages | 20 | Investigate | Power fail log entries |
| Power Cycle Events | 1483 | Investigate | Codes 1 & 2 |
| Harmonic Exceedances (H5/H7) | 0 | Low | All within limit |
| Metric | Target | Actual | Status |
|---|---|---|---|
| VTHD Compliance | ≤ 5% | 1.2% | Compliant |
| Voltage Unbalance | ≤ 2% | — | Pending |
| PQ Threshold Events | ≤ 40 / quarter | 84 | Non-Compliant |
| Outages | ≤ 20 / quarter | 20 | Compliant |
| Harmonic Incidents (H5/H7) | ≤ 10 | 0 | Within Limit |