Meter PQ ReportStanger-Sappi Feed 1 (33KV)
Doc No:MCOR-PQ-0010
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-08-28 07:55:06 SAST
Meter Serial: 10266111
Site: Kwadukuza Municipality
Feeder: 5
Area: Stanger Substation
Last Reading: 2026-08-28 07:54
Quarter: Q2 2026

10.3   Voltage Compliance

ParameterNERSA LimitMeasuredStatus
Voltage PQ Events (threshold log)≤ 40 / quarter23257 eventsNon-Compliant
Power Failures / Outages≤ 20 / quarter11298 eventsNon-Compliant
Voltage Unbalance≤ 2%1.72%Compliant
Flicker Pst (short-term)≤ 1.0Max 0.00Compliant
Flicker Plt (long-term)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitL1L2L3Status
THD Voltage (VTHD)≤ 5% 0.5%0.8%0.5% Compliant
3rd Harmonic (V)Review 0.3%0.6%0.1% Compliant
5th Harmonic (V)≤ 3% 0.2%0.3%0.3% Compliant
7th Harmonic (V)≤ 3% 0.2%0.2%0.2% Compliant

10.5   Loading & Power Factor

ParameterL1L2L3Value
Voltage (V)19554.0V19788.0V19893.0VUnbal: 1.72%
Current (A)30.500A31.500A30.000A
Active PowerTotal: 1129.500 kWPF: 0.623
Frequency49.840 HzCompliant

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events23257HighDLMS event log codes 210-213
Power Failures / Outages11298HighPower fail log entries
Power Cycle Events14894InvestigateCodes 1 & 2
Harmonic Exceedances (H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
VTHD Compliance≤ 5%0.8%Compliant
Voltage Unbalance≤ 2%1.72%Compliant
PQ Threshold Events≤ 40 / quarter23257Non-Compliant
Outages≤ 20 / quarter11298Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit