Meter PQ ReportShakaskraal-Feeder 2 (South) (33KV)
Doc No:MCOR-PQ-0012
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-07-22 20:18:58 SAST
Meter Serial: 10266110
Site: Kwadukuza Municipality
Feeder: 8
Area: Shakaskraal Substation
Last Reading: 2026-07-22 20:13
Quarter: Q2 2026

10.3   Voltage Compliance

ParameterNERSA LimitMeasuredStatus
Voltage PQ Events (threshold log)≤ 40 / quarter29469 eventsNon-Compliant
Power Failures / Outages≤ 20 / quarter17313 eventsNon-Compliant
Voltage Unbalance≤ 2%Pending
Flicker Pst (short-term)≤ 1.0Max 0.00Compliant
Flicker Plt (long-term)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitL1L2L3Status
THD Voltage (VTHD)≤ 5% 1.0%0.0%1.1% Compliant
3rd Harmonic (V)Review 0.4%0.0%0.1% Compliant
5th Harmonic (V)≤ 3% 0.7%0.0%0.9% Compliant
7th Harmonic (V)≤ 3% 0.3%0.0%0.4% Compliant

10.5   Loading & Power Factor

ParameterL1L2L3Value
Voltage (V)34008.0V0.0V34221.0VUnbal: —
Current (A)409.600A9.600A403.200A
Active PowerTotal: 23313.600 kWPF: 0.844
Frequency50.070 HzCompliant

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events29469HighDLMS event log codes 210-213
Power Failures / Outages17313HighPower fail log entries
Power Cycle Events21163InvestigateCodes 1 & 2
Harmonic Exceedances (H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
VTHD Compliance≤ 5%1.1%Compliant
Voltage Unbalance≤ 2%Pending
PQ Threshold Events≤ 40 / quarter29469Non-Compliant
Outages≤ 20 / quarter17313Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit