Meter PQ ReportStanger-Gelnhills Feed (33KV)
Doc No:MCOR-PQ-0011
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-06-23 14:20:06 SAST
Meter Serial: 10266109
Site: Kwadukuza Municipality
Feeder: 3
Area: Stanger Substation
Last Reading: 2026-06-23 14:18
Quarter: Q2 2026

10.3   Voltage Compliance

ParameterNERSA LimitMeasuredStatus
Voltage PQ Events (threshold log)≤ 40 / quarter12 eventsCompliant
Power Failures / Outages≤ 20 / quarter0 eventsCompliant
Voltage Unbalance≤ 2%1.68%Compliant
Flicker Pst (short-term)≤ 1.0Max 0.00Compliant
Flicker Plt (long-term)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitL1L2L3Status
THD Voltage (VTHD)≤ 5% 0.5%0.8%0.5% Compliant
3rd Harmonic (V)Review 0.2%0.6%0.1% Compliant
5th Harmonic (V)≤ 3% 0.3%0.3%0.3% Compliant
7th Harmonic (V)≤ 3% 0.0%0.0%0.1% Compliant

10.5   Loading & Power Factor

ParameterL1L2L3Value
Voltage (V)19569.0V19836.0V19902.0VUnbal: 1.68%
Current (A)208.800A218.000A214.000A
Active PowerTotal: 11950.800 kWPF: 0.934
Frequency49.850 HzCompliant

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events12InvestigateDLMS event log codes 210-213
Power Failures / Outages0LowPower fail log entries
Power Cycle Events30InvestigateCodes 1 & 2
Harmonic Exceedances (H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
VTHD Compliance≤ 5%0.8%Compliant
Voltage Unbalance≤ 2%1.68%Compliant
PQ Threshold Events≤ 40 / quarter12Compliant
Outages≤ 20 / quarter0Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit