Meter PQ ReportStanger-Groutville Phase1 (33KV)
Doc No:MCOR-PQ-0009
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-08-28 07:55:17 SAST
Meter Serial: 10266107
Site: Kwadukuza Municipality
Feeder: 4
Area: Stanger Substation
Last Reading: 2026-08-28 07:43
Quarter: Q2 2026

10.3   Voltage Compliance

ParameterNERSA LimitMeasuredStatus
Voltage PQ Events (threshold log)≤ 40 / quarter1133 eventsNon-Compliant
Power Failures / Outages≤ 20 / quarter885 eventsNon-Compliant
Voltage Unbalance≤ 2%5.26%Non-Compliant
Flicker Pst (short-term)≤ 1.0Max 0.00Compliant
Flicker Plt (long-term)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitL1L2L3Status
THD Voltage (VTHD)≤ 5% 0.6%1.4%0.9% Compliant
3rd Harmonic (V)Review 0.5%1.3%0.7% Compliant
5th Harmonic (V)≤ 3% 0.2%0.3%0.4% Compliant
7th Harmonic (V)≤ 3% 0.2%0.1%0.1% Compliant

10.5   Loading & Power Factor

ParameterL1L2L3Value
Voltage (V)19665.0V19326.0V20367.0VUnbal: 5.26%
Current (A)181.600A189.600A183.200A
Active PowerTotal: 10401.600 kWPF: 0.943
Frequency49.930 HzCompliant

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events1133HighDLMS event log codes 210-213
Power Failures / Outages885HighPower fail log entries
Power Cycle Events2450InvestigateCodes 1 & 2
Harmonic Exceedances (H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
VTHD Compliance≤ 5%1.4%Compliant
Voltage Unbalance≤ 2%5.26%Non-Compliant
PQ Threshold Events≤ 40 / quarter1133Non-Compliant
Outages≤ 20 / quarter885Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit