Meter PQ ReportStanger-Feeder 2 (33kV)
Doc No:MCOR-PQ-0003
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-08-22 13:20:26 SAST
Meter Serial: 10266104
Site: Kwadukuza Municipality
Feeder: 2
Area: Stanger Substation
Last Reading: 2026-08-22 13:02
Quarter: Q2 2026

10.3   Voltage Compliance

ParameterNERSA LimitMeasuredStatus
Voltage PQ Events (threshold log)≤ 40 / quarter27312 eventsNon-Compliant
Power Failures / Outages≤ 20 / quarter10638 eventsNon-Compliant
Voltage Unbalance≤ 2%1.37%Compliant
Flicker Pst (short-term)≤ 1.0Max 0.00Compliant
Flicker Plt (long-term)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitL1L2L3Status
THD Voltage (VTHD)≤ 5% 0.7%0.8%0.6% Compliant
3rd Harmonic (V)Review 0.3%0.6%0.2% Compliant
5th Harmonic (V)≤ 3% 0.5%0.4%0.4% Compliant
7th Harmonic (V)≤ 3% 0.2%0.2%0.3% Compliant

10.5   Loading & Power Factor

ParameterL1L2L3Value
Voltage (V)20019.0V19944.0V19746.0VUnbal: 1.37%
Current (A)96.000A97.600A95.600A
Active PowerTotal: 5404.800 kWPF: 0.939
Frequency50.150 HzCompliant

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events27312HighDLMS event log codes 210-213
Power Failures / Outages10638HighPower fail log entries
Power Cycle Events8253InvestigateCodes 1 & 2
Harmonic Exceedances (H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
VTHD Compliance≤ 5%0.8%Compliant
Voltage Unbalance≤ 2%1.37%Compliant
PQ Threshold Events≤ 40 / quarter27312Non-Compliant
Outages≤ 20 / quarter10638Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit