| Doc No: | MCOR-PQ-0004 |
| Document Ref: | MCOR-PQ-2026-Q2 |
| Period: | 2026-04-01 to 2026-06-30 |
| Generated | 2026-09-07 09:33:08 SAST |
| Parameter | NERSA Limit | Measured | Status |
|---|---|---|---|
| Voltage PQ Events (threshold log) | ≤ 40 / quarter | 324 events | Non-Compliant |
| Power Failures / Outages | ≤ 20 / quarter | 26 events | Non-Compliant |
| Voltage Unbalance | ≤ 2% | — | Pending |
| Flicker Pst (short-term) | ≤ 1.0 | Max 0.00 | Compliant |
| Flicker Plt (long-term) | ≤ 0.8 | 0.00 | Compliant |
| Parameter | NERSA Limit | L1 | L2 | L3 | Status |
|---|---|---|---|---|---|
| THD Voltage (VTHD) | ≤ 5% | 1.4% | 0.0% | 1.3% | Compliant |
| 3rd Harmonic (V) | Review | 0.8% | 0.0% | 0.2% | Compliant |
| 5th Harmonic (V) | ≤ 3% | 0.9% | 0.0% | 0.9% | Compliant |
| 7th Harmonic (V) | ≤ 3% | 0.6% | 0.0% | 0.7% | Compliant |
| Parameter | L1 | L2 | L3 | Value |
|---|---|---|---|---|
| Voltage (V) | 32937.0V | 0.0V | 32343.0V | Unbal: — |
| Current (A) | 357.200A | 0.000A | 350.400A | — |
| Active Power | Total: 19396.800 kW | PF: 0.848 | ||
| Frequency | 49.720 Hz | Compliant | ||
| Event Type | Count | Severity | Notes |
|---|---|---|---|
| Voltage PQ Threshold Events | 324 | High | DLMS event log codes 210-213 |
| Power Failures / Outages | 26 | High | Power fail log entries |
| Power Cycle Events | 318 | Investigate | Codes 1 & 2 |
| Harmonic Exceedances (H5/H7) | 0 | Low | All within limit |
| Metric | Target | Actual | Status |
|---|---|---|---|
| VTHD Compliance | ≤ 5% | 1.4% | Compliant |
| Voltage Unbalance | ≤ 2% | — | Pending |
| PQ Threshold Events | ≤ 40 / quarter | 324 | Non-Compliant |
| Outages | ≤ 20 / quarter | 26 | Non-Compliant |
| Harmonic Incidents (H5/H7) | ≤ 10 | 0 | Within Limit |