← Back to ReportsSaved report — pq_meter_10266102_Q2_2026_20260623.html
⚡ Mcor Power Quality Portal
Kwadukuza Municipality
Logged in as Corrie Logout
← Back to Meter Report Hub ⬇ Export Excel
MCOR Power Quality
Meter PQ ReportZimbali Sub Incomer (Feeder 2) (33KV)
Doc No:MCOR-PQ-0004
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-06-23 07:27:05 SAST
Meter Serial: 10266102
Site: Kwadukuza Municipality
Feeder: 10
Area: Driefontein Substation's
Last Reading: 2026-06-23 07:17
Quarter: Q2 2026

10.3   Voltage Compliance

ParameterNERSA LimitMeasuredStatus
Voltage PQ Events (threshold log)≤ 40 / quarter6 eventsCompliant
Power Failures / Outages≤ 20 / quarter0 eventsCompliant
Voltage Unbalance≤ 2%Pending
Flicker Pst (short-term)≤ 1.0Max 0.00Compliant
Flicker Plt (long-term)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitL1L2L3Status
THD Voltage (VTHD)≤ 5% 2.4%0.0%2.4% Compliant
3rd Harmonic (V)Review 0.5%0.0%0.1% Compliant
5th Harmonic (V)≤ 3% 2.0%0.0%2.1% Compliant
7th Harmonic (V)≤ 3% 1.2%0.0%1.2% Compliant

10.5   Loading & Power Factor

ParameterL1L2L3Value
Voltage (V)33933.0V0.0V33420.0VUnbal: —
Current (A)218.400A0.000A207.200A
Active PowerTotal: 12230.400 kWPF: 0.850
Frequency50.120 HzCompliant

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events6InvestigateDLMS event log codes 210-213
Power Failures / Outages0LowPower fail log entries
Power Cycle Events4InvestigateCodes 1 & 2
Harmonic Exceedances (H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
VTHD Compliance≤ 5%2.4%Compliant
Voltage Unbalance≤ 2%Pending
PQ Threshold Events≤ 40 / quarter6Compliant
Outages≤ 20 / quarter0Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit