| Document #: | — |
| Period: | 2026-07-01 to 2026-09-30 |
| Generated | 2026-06-22 12:41:53 SAST |
| Parameter | NERSA Limit | Measured Range | Compliance Status |
|---|---|---|---|
| Voltage PQ Events (threshold log) | ≤ 40 events per quarter | 0 events | Compliant |
| Power Failures / Outages | ≤ 20 events per quarter | 0 events | Compliant |
| Voltage Unbalance (max site) | ≤ 2% | 7.85% | Non-Compliant |
| Flicker Pst (short-term, max site) | ≤ 1.0 | 0.00 | Compliant |
| Flicker Plt (long-term, max site) | ≤ 0.8 | 0.00 | Compliant |
| Parameter | NERSA Limit | Measured Max (all meters) | Phases Exceeding Limit | Compliance Status |
|---|---|---|---|---|
| THD Voltage (VTHD) | ≤ 5% | Max 1.4% | 0 | Compliant |
| 3rd Harmonic (V) | Review | Max 0.6% | 0 | Compliant |
| 5th Harmonic (V) | ≤ 3% | Max 0.9% | 0 | Compliant |
| 7th Harmonic (V) | ≤ 3% | Max 0.8% | 0 | Compliant |
| Meter / Feeder | Voltage / Current / kW Snapshot | VTHD & PF | Compliance Status |
|---|---|---|---|
| Stanger-Feeder 1 (33KV) / 2 Stanger Substation |
V: 19509.0V / 19713.0V / 19818.0V I: 53.00A / 56.00A / 54.50A kW: 3222.000 kW Unbal: 1.57% as at 2026-06-22 14:32 |
VTHD: 0.6% / 0.9% / 0.7% PF: 0.985 |
Compliant |
| Stanger-Feeder 2 (33kV) / 2 Stanger Substation |
V: 19833.0V / 19671.0V / 19506.0V I: 102.80A / 100.40A / 99.20A kW: 5838.000 kW Unbal: 1.66% as at 2026-06-22 14:36 |
VTHD: — / — / — PF: 0.950 |
Compliant |
| Stanger-Gelnhills Feed (33KV) / 2 Stanger Substation |
V: 19536.0V / 19701.0V / 19833.0V I: 210.80A / 218.00A / 217.20A kW: 12008.400 kW Unbal: 1.51% as at 2026-06-22 14:36 |
VTHD: 0.7% / 0.8% / 0.6% PF: 0.944 |
Compliant |
| Stanger-Groutville Phase1 (33KV) / 2 Stanger Substation |
V: 19542.0V / 18939.0V / 20481.0V I: 200.00A / 204.80A / 201.60A kW: 11328.000 kW Unbal: 7.85% as at 2026-06-22 14:40 |
VTHD: — / — / — PF: 0.943 |
Compliant |
| Stanger-Sappi Feed 1 (33KV) / 2 Stanger Substation |
V: 19506.0V / 19710.0V / 19830.0V I: 132.50A / 150.00A / 145.00A kW: 8359.500 kW Unbal: 1.65% as at 2026-06-22 14:29 |
VTHD: — / — / — PF: 0.984 |
Compliant |
| Stanger-Sappi Feed 2 (33KV) / 2 Stanger Substation |
V: 19476.0V / 19698.0V / 19791.0V I: 142.50A / 150.50A / 140.00A kW: 8313.000 kW Unbal: 1.60% as at 2026-06-22 14:33 |
VTHD: — / — / — PF: 0.981 |
Compliant |
| Shakaskraal-Feeder 1 (North) (33KV) / 1 Shakaskraal Substation |
V: 34029.0V / 0.0V / 34272.0V I: 96.00A / 0.00A / 92.80A kW: 5280.000 kW Unbal: — as at 2026-06-22 14:31 |
VTHD: — / — / — PF: 0.811 |
Low PF Warning |
| Shakaskraal-Feeder 2 (South) (33KV) / 1 Shakaskraal Substation |
V: 34419.0V / 0.0V / 34638.0V I: 382.40A / 8.00A / 376.00A kW: 21628.800 kW Unbal: — as at 2026-06-22 14:29 |
VTHD: — / — / — PF: 0.827 |
Low PF Warning |
| Ballito Sub Incomer (Feeder 1) (33KV) / 3 Driefontein Substation's |
V: 33672.0V / 0.0V / 34449.0V I: 79.80A / 0.00A / 79.80A kW: 4476.600 kW Unbal: — as at 2026-06-22 14:33 |
VTHD: 1.3% / 0.0% / 1.4% PF: 0.840 |
Low PF Warning |
| Zimbali Sub Incomer (Feeder 2) (33KV) / 3 Driefontein Substation's |
V: 34020.0V / 0.0V / 33555.0V I: 242.40A / 0.00A / 229.20A kW: 13744.800 kW Unbal: — as at 2026-06-22 14:32 |
VTHD: 1.2% / 0.0% / 1.3% PF: 0.844 |
Low PF Warning |
| Site Combined Totals |
Mean Voltage: 20904.90 V Total Current: 4165.2 A Total kW: 94199.100 kW |
Mean PF: 0.911 | Live |
| Event Type | Count | Severity | Notes |
|---|---|---|---|
| Voltage PQ Threshold Events | 0 | Low | DLMS event log codes 210-213 |
| Power Failures / Outages | 0 | Low | Power fail log entries |
| Power Cycle Events (Up/Down) | 0 | Low | Standard event codes 1 & 2 |
| Harmonic Exceedances (V H5/H7) | 0 | Low | All within limit |
| Metric | Target | Actual | Status |
|---|---|---|---|
| Meters Compliant (VTHD) | ≥ 95% | 100.0% | Compliant |
| Voltage Unbalance | ≤ 2% | 7.85% | Non-Compliant |
| PQ Threshold Events | ≤ 40 / quarter | 0 | Compliant |
| Outages | ≤ 20 / quarter | 0 | Compliant |
| Harmonic Incidents (H5/H7) | ≤ 10 | 0 | Within Limit |