← Back to ReportsSaved report — pq_combined_Q3_2026_20260622.html
⚡ Mcor Power Quality Portal
Kwadukuza Municipality
Logged in as Corrie Logout
MCOR Power Quality
PQ Mon ReportQ3 2026
Document #:
Period:2026-07-01 to 2026-09-30
Generated2026-06-22 12:41:53 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter0 eventsCompliant
Power Failures / Outages≤ 20 events per quarter0 eventsCompliant
Voltage Unbalance (max site)≤ 2%7.85%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.4%0Compliant
3rd Harmonic (V)ReviewMax 0.6%0Compliant
5th Harmonic (V)≤ 3%Max 0.9%0Compliant
7th Harmonic (V)≤ 3%Max 0.8%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / 2
Stanger Substation
V: 19509.0V / 19713.0V / 19818.0V
I: 53.00A / 56.00A / 54.50A
kW: 3222.000 kW  Unbal: 1.57%
as at 2026-06-22 14:32
VTHD: 0.6% / 0.9% / 0.7%
PF: 0.985
Compliant
Stanger-Feeder 2 (33kV) / 2
Stanger Substation
V: 19833.0V / 19671.0V / 19506.0V
I: 102.80A / 100.40A / 99.20A
kW: 5838.000 kW  Unbal: 1.66%
as at 2026-06-22 14:36
VTHD: — / — / —
PF: 0.950
Compliant
Stanger-Gelnhills Feed (33KV) / 2
Stanger Substation
V: 19536.0V / 19701.0V / 19833.0V
I: 210.80A / 218.00A / 217.20A
kW: 12008.400 kW  Unbal: 1.51%
as at 2026-06-22 14:36
VTHD: 0.7% / 0.8% / 0.6%
PF: 0.944
Compliant
Stanger-Groutville Phase1 (33KV) / 2
Stanger Substation
V: 19542.0V / 18939.0V / 20481.0V
I: 200.00A / 204.80A / 201.60A
kW: 11328.000 kW  Unbal: 7.85%
as at 2026-06-22 14:40
VTHD: — / — / —
PF: 0.943
Compliant
Stanger-Sappi Feed 1 (33KV) / 2
Stanger Substation
V: 19506.0V / 19710.0V / 19830.0V
I: 132.50A / 150.00A / 145.00A
kW: 8359.500 kW  Unbal: 1.65%
as at 2026-06-22 14:29
VTHD: — / — / —
PF: 0.984
Compliant
Stanger-Sappi Feed 2 (33KV) / 2
Stanger Substation
V: 19476.0V / 19698.0V / 19791.0V
I: 142.50A / 150.50A / 140.00A
kW: 8313.000 kW  Unbal: 1.60%
as at 2026-06-22 14:33
VTHD: — / — / —
PF: 0.981
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / 1
Shakaskraal Substation
V: 34029.0V / 0.0V / 34272.0V
I: 96.00A / 0.00A / 92.80A
kW: 5280.000 kW  Unbal: —
as at 2026-06-22 14:31
VTHD: — / — / —
PF: 0.811
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / 1
Shakaskraal Substation
V: 34419.0V / 0.0V / 34638.0V
I: 382.40A / 8.00A / 376.00A
kW: 21628.800 kW  Unbal: —
as at 2026-06-22 14:29
VTHD: — / — / —
PF: 0.827
Low PF Warning
Ballito Sub Incomer (Feeder 1) (33KV) / 3
Driefontein Substation's
V: 33672.0V / 0.0V / 34449.0V
I: 79.80A / 0.00A / 79.80A
kW: 4476.600 kW  Unbal: —
as at 2026-06-22 14:33
VTHD: 1.3% / 0.0% / 1.4%
PF: 0.840
Low PF Warning
Zimbali Sub Incomer (Feeder 2) (33KV) / 3
Driefontein Substation's
V: 34020.0V / 0.0V / 33555.0V
I: 242.40A / 0.00A / 229.20A
kW: 13744.800 kW  Unbal: —
as at 2026-06-22 14:32
VTHD: 1.2% / 0.0% / 1.3%
PF: 0.844
Low PF Warning
Site Combined Totals Mean Voltage: 20904.90 V
Total Current: 4165.2 A
Total kW: 94199.100 kW
Mean PF: 0.911 Live

10.6   PQ Event Summary (2026-07-01 to 2026-09-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events0LowDLMS event log codes 210-213
Power Failures / Outages0LowPower fail log entries
Power Cycle Events (Up/Down)0LowStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%7.85%Non-Compliant
PQ Threshold Events≤ 40 / quarter0Compliant
Outages≤ 20 / quarter0Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit