PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-10-31 12:54:24 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter158891 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter83853 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%7.26%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.4%0Compliant
3rd Harmonic (V)ReviewMax 1.3%0Compliant
5th Harmonic (V)≤ 3%Max 0.8%0Compliant
7th Harmonic (V)≤ 3%Max 0.8%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19617.0V / 19827.0V / 19884.0V
I: 132.50A / 136.00A / 133.50A
kW: 7414.500 kW  Unbal: 1.35%
as at 2026-10-30 15:48
VTHD: 0.7% / 0.8% / 0.6%
PF: 0.929
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 19914.0V / 19869.0V / 19674.0V
I: 120.40A / 122.80A / 121.20A
kW: 6760.800 kW  Unbal: 1.21%
as at 2026-10-30 15:31
VTHD: 0.7% / 0.8% / 0.7%
PF: 0.928
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19698.0V / 19893.0V / 19953.0V
I: 106.00A / 109.20A / 108.00A
kW: 6114.000 kW  Unbal: 1.28%
as at 2026-10-30 15:39
VTHD: 0.7% / 0.8% / 0.6%
PF: 0.951
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19893.0V / 19128.0V / 20571.0V
I: 209.60A / 217.60A / 204.00A
kW: 11553.600 kW  Unbal: 7.26%
as at 2026-10-30 15:35
VTHD: 1.0% / 1.4% / 1.0%
PF: 0.921
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19608.0V / 19842.0V / 19863.0V
I: 145.00A / 155.00A / 147.00A
kW: 8610.000 kW  Unbal: 1.29%
as at 2026-10-30 15:32
VTHD: 0.7% / 0.8% / 0.7%
PF: 0.981
Compliant
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19623.0V / 19863.0V / 19872.0V
I: 140.00A / 152.00A / 141.00A
kW: 8302.500 kW  Unbal: 1.26%
as at 2026-10-30 15:33
VTHD: 0.7% / 0.8% / 0.7%
PF: 0.978
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 33963.0V / 0.0V / 33963.0V
I: 100.80A / 0.00A / 99.20A
kW: 5520.000 kW  Unbal: —
as at 2026-10-30 15:37
VTHD: 0.8% / 0.0% / 0.9%
PF: 0.805
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 34038.0V / 0.0V / 34038.0V
I: 342.40A / 8.00A / 334.40A
kW: 18686.400 kW  Unbal: —
as at 2026-10-30 15:30
VTHD: 0.8% / 0.0% / 1.0%
PF: 0.821
Low PF Warning
Ballito Sub (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 33618.0V / 0.0V / 34347.0V
I: 86.40A / 0.00A / 87.00A
kW: 4921.200 kW  Unbal: —
as at 2026-10-30 15:46
VTHD: 1.0% / 0.0% / 1.0%
PF: 0.839
Low PF Warning
Zimbali Sub (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 33660.0V / 0.0V / 33102.0V
I: 241.60A / 0.00A / 229.20A
kW: 13126.800 kW  Unbal: —
as at 2026-10-30 15:47
VTHD: 1.1% / 0.0% / 1.0%
PF: 0.834
Low PF Warning
Site Combined Totals Mean Voltage: 20910.70 V
Total Current: 4129.8 A
Total kW: 91009.800 kW
Mean PF: 0.899 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events158891HighDLMS event log codes 210-213
Power Failures / Outages83853HighPower fail log entries
Power Cycle Events (Up/Down)107549InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%7.26%Non-Compliant
PQ Threshold Events≤ 40 / quarter158891Non-Compliant
Outages≤ 20 / quarter83853Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit