← Back to ReportsSaved report — pq_combined_Q2_2026_20260922.html
⚡ Mcor Power Quality
Kwadukuza Municipality
Logged in as Corrie Logout
MCOR Power Quality
PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-09-22 13:50:27 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter158891 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter83853 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%6.30%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.6%0Compliant
3rd Harmonic (V)ReviewMax 1.4%0Compliant
5th Harmonic (V)≤ 3%Max 0.8%0Compliant
7th Harmonic (V)≤ 3%Max 0.7%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19518.0V / 19713.0V / 19797.0V
I: 144.00A / 151.50A / 148.00A
kW: —  Unbal: 1.42%
as at 2026-09-22 13:37
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.942
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 19854.0V / 19755.0V / 19590.0V
I: 119.60A / 120.40A / 117.60A
kW: 6678.000 kW  Unbal: 1.34%
as at 2026-09-22 13:31
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.951
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19512.0V / 19710.0V / 19794.0V
I: 88.40A / 90.40A / 90.80A
kW: 5086.800 kW  Unbal: 1.43%
as at 2026-09-22 13:37
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.959
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19584.0V / 19086.0V / 20325.0V
I: 186.40A / 190.40A / 184.00A
kW: 10276.800 kW  Unbal: 6.30%
as at 2026-09-22 13:48
VTHD: 0.9% / 1.6% / 1.0%
PF: 0.935
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19449.0V / 19647.0V / 19731.0V
I: 125.00A / 135.50A / 128.50A
kW: 7639.500 kW  Unbal: 1.44%
as at 2026-09-22 13:48
VTHD: 0.6% / 0.9% / 0.6%
PF: 0.993
Compliant
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19485.0V / 19674.0V / 19761.0V
I: 120.50A / 131.50A / 123.00A
kW: 7248.000 kW  Unbal: 1.41%
as at 2026-09-22 13:40
VTHD: 0.7% / 0.9% / 0.6%
PF: 0.989
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 34158.0V / 0.0V / 34359.0V
I: 81.60A / 0.00A / 81.60A
kW: 4526.400 kW  Unbal: —
as at 2026-09-22 13:32
VTHD: 0.8% / 0.0% / 0.8%
PF: 0.807
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 34311.0V / 0.0V / 34419.0V
I: 366.40A / 8.00A / 358.40A
kW: 20150.400 kW  Unbal: —
as at 2026-09-22 13:48
VTHD: 0.9% / 0.0% / 0.9%
PF: 0.803
Low PF Warning
Ballito Sub (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 33834.0V / 0.0V / 34518.0V
I: 79.80A / 0.00A / 78.60A
kW: 4518.000 kW  Unbal: —
as at 2026-09-22 13:30
VTHD: 0.9% / 0.0% / 1.0%
PF: 0.835
Low PF Warning
Zimbali Sub (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 33594.0V / 0.0V / 33081.0V
I: 208.40A / 0.00A / 198.00A
kW: 11691.600 kW  Unbal: —
as at 2026-09-22 13:45
VTHD: 1.0% / 0.0% / 0.9%
PF: 0.841
Low PF Warning
Site Combined Totals Mean Voltage: 20875.30 V
Total Current: 3856.3 A
Total kW: 77815.500 kW
Mean PF: 0.905 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events158891HighDLMS event log codes 210-213
Power Failures / Outages83853HighPower fail log entries
Power Cycle Events (Up/Down)107549InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%6.30%Non-Compliant
PQ Threshold Events≤ 40 / quarter158891Non-Compliant
Outages≤ 20 / quarter83853Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit