← Back to ReportsSaved report — pq_combined_Q2_2026_20260921.html
⚡ Mcor Power Quality
Kwadukuza Municipality
Logged in as Corrie Logout
MCOR Power Quality
PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-09-21 12:06:43 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter158891 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter83853 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%6.26%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.5%0Compliant
3rd Harmonic (V)ReviewMax 1.4%0Compliant
5th Harmonic (V)≤ 3%Max 0.8%0Compliant
7th Harmonic (V)≤ 3%Max 0.7%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19548.0V / 19722.0V / 19809.0V
I: 127.00A / 134.00A / 131.00A
kW: 7396.500 kW  Unbal: 1.33%
as at 2026-09-21 11:48
VTHD: 0.6% / 0.9% / 0.6%
PF: 0.931
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 19845.0V / 19710.0V / 19437.0V
I: 120.40A / 120.40A / 116.00A
kW: 6627.600 kW  Unbal: 2.07%
as at 2026-09-21 12:02
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.938
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19530.0V / 19749.0V / 19806.0V
I: 88.80A / 87.60A / 86.80A
kW: 4944.000 kW  Unbal: 1.40%
as at 2026-09-21 11:50
VTHD: 0.6% / 0.9% / 0.6%
PF: 0.953
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19470.0V / 19137.0V / 20367.0V
I: 149.60A / 154.40A / 146.40A
kW: 8196.000 kW  Unbal: 6.26%
as at 2026-09-21 12:03
VTHD: 0.9% / 1.5% / 1.1%
PF: 0.925
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19563.0V / 19743.0V / 19827.0V
I: 146.50A / 157.00A / 151.00A
kW: 8709.000 kW  Unbal: 1.34%
as at 2026-09-21 11:51
VTHD: 0.5% / 0.8% / 0.6%
PF: 0.978
Compliant
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19470.0V / 19728.0V / 19770.0V
I: 140.50A / 155.00A / 143.50A
kW: 8460.000 kW  Unbal: 1.53%
as at 2026-09-21 11:55
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.973
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 33657.0V / 0.0V / 33771.0V
I: 75.20A / 0.00A / 73.60A
kW: 4099.200 kW  Unbal: —
as at 2026-09-21 11:46
VTHD: 0.8% / 0.0% / 0.8%
PF: 0.803
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 34062.0V / 0.0V / 34197.0V
I: 318.40A / 6.40A / 313.60A
kW: 17568.000 kW  Unbal: —
as at 2026-09-21 11:57
VTHD: 0.9% / 0.0% / 0.9%
PF: 0.827
Low PF Warning
Ballito Sub (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 33339.0V / 0.0V / 33993.0V
I: 94.20A / 0.00A / 96.00A
kW: 5380.200 kW  Unbal: —
as at 2026-09-21 11:39
VTHD: 1.0% / 0.0% / 1.1%
PF: 0.850
Compliant
Zimbali Sub (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 33588.0V / 0.0V / 33162.0V
I: 215.20A / 0.00A / 203.60A
kW: 11892.000 kW  Unbal: —
as at 2026-09-21 11:56
VTHD: 1.0% / 0.0% / 0.9%
PF: 0.842
Low PF Warning
Site Combined Totals Mean Voltage: 20800.00 V
Total Current: 3752.1 A
Total kW: 83272.500 kW
Mean PF: 0.902 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events158891HighDLMS event log codes 210-213
Power Failures / Outages83853HighPower fail log entries
Power Cycle Events (Up/Down)107549InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%6.26%Non-Compliant
PQ Threshold Events≤ 40 / quarter158891Non-Compliant
Outages≤ 20 / quarter83853Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit