MCOR Power Quality
PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-09-07 09:20:30 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter158891 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter83853 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%3.60%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.4%0Compliant
3rd Harmonic (V)ReviewMax 1.4%0Compliant
5th Harmonic (V)≤ 3%Max 1.0%0Compliant
7th Harmonic (V)≤ 3%Max 0.7%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19395.0V / 19635.0V / 19656.0V
I: 156.50A / 161.00A / 159.00A
kW: 9075.000 kW  Unbal: 1.33%
as at 2026-09-07 09:04
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.960
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 19860.0V / 19848.0V / 19596.0V
I: 112.80A / 118.00A / 113.60A
kW: 6604.800 kW  Unbal: 1.34%
as at 2026-09-07 09:12
VTHD: 0.4% / 0.8% / 0.4%
PF: 0.959
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19380.0V / 19644.0V / 19644.0V
I: 118.00A / 121.20A / 116.40A
kW: 6796.800 kW  Unbal: 1.35%
as at 2026-09-07 09:03
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.974
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19518.0V / 19293.0V / 19998.0V
I: 189.60A / 200.80A / 193.60A
kW: 10850.400 kW  Unbal: 3.60%
as at 2026-09-07 09:01
VTHD: 0.6% / 1.4% / 0.8%
PF: 0.949
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19602.0V / 19839.0V / 19854.0V
I: 145.00A / 154.00A / 147.00A
kW: 8689.500 kW  Unbal: 1.27%
as at 2026-09-07 09:12
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.986
Compliant
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19566.0V / 19845.0V / 19872.0V
I: 135.50A / 149.00A / 136.50A
kW: 8265.000 kW  Unbal: 1.55%
as at 2026-09-07 09:17
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.984
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 33435.0V / 0.0V / 33477.0V
I: 88.00A / 0.00A / 84.80A
kW: 4804.800 kW  Unbal: —
as at 2026-09-07 09:13
VTHD: 0.7% / 0.0% / 0.7%
PF: 0.832
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 33795.0V / 0.0V / 33846.0V
I: 462.40A / 11.20A / 451.20A
kW: 26059.200 kW  Unbal: —
as at 2026-09-07 09:06
VTHD: 0.9% / 0.0% / 0.9%
PF: 0.845
Low PF Warning
Ballito Sub (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 32082.0V / 0.0V / 32829.0V
I: 0.00A / 0.00A / 0.00A
kW: 0.000 kW  Unbal: —
as at 2026-09-07 09:12
VTHD: 1.3% / 0.0% / 1.4%
PF: -0.017
Low PF Warning
Zimbali Sub (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 32886.0V / 0.0V / 32220.0V
I: 347.20A / 0.00A / 338.00A
kW: 18991.200 kW  Unbal: —
as at 2026-09-07 09:00
VTHD: 1.4% / 0.0% / 1.3%
PF: 0.849
Low PF Warning
Site Combined Totals Mean Voltage: 20620.50 V
Total Current: 4410.3 A
Total kW: 100136.700 kW
Mean PF: 0.832 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events158891HighDLMS event log codes 210-213
Power Failures / Outages83853HighPower fail log entries
Power Cycle Events (Up/Down)107549InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%3.60%Non-Compliant
PQ Threshold Events≤ 40 / quarter158891Non-Compliant
Outages≤ 20 / quarter83853Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit