MCOR Power Quality
PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-08-28 07:56:10 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter158891 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter83853 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%5.26%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.5%0Compliant
3rd Harmonic (V)ReviewMax 1.3%0Compliant
5th Harmonic (V)≤ 3%Max 1.1%0Compliant
7th Harmonic (V)≤ 3%Max 0.9%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19599.0V / 19830.0V / 19962.0V
I: 178.50A / 187.50A / 184.00A
kW: 10531.500 kW  Unbal: 1.83%
as at 2026-08-28 07:43
VTHD: 0.5% / 0.8% / 0.5%
PF: 0.964
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 19953.0V / 19821.0V / 19593.0V
I: 100.40A / 104.00A / 100.40A
kW: 5810.400 kW  Unbal: 1.82%
as at 2026-08-28 07:47
VTHD: 0.5% / 0.7% / 0.5%
PF: 0.960
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19590.0V / 19854.0V / 19959.0V
I: 86.00A / 84.00A / 82.40A
kW: 4812.000 kW  Unbal: 1.86%
as at 2026-08-28 07:38
VTHD: 0.5% / 0.9% / 0.5%
PF: 0.961
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19665.0V / 19326.0V / 20367.0V
I: 181.60A / 189.60A / 183.20A
kW: 10401.600 kW  Unbal: 5.26%
as at 2026-08-28 07:43
VTHD: 0.6% / 1.4% / 0.9%
PF: 0.943
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19554.0V / 19788.0V / 19893.0V
I: 30.50A / 31.50A / 30.00A
kW: 1129.500 kW  Unbal: 1.72%
as at 2026-08-28 07:54
VTHD: 0.5% / 0.8% / 0.5%
PF: 0.623
Low PF Warning
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19560.0V / 19788.0V / 19899.0V
I: 29.00A / 30.50A / 28.50A
kW: 1140.000 kW  Unbal: 1.72%
as at 2026-08-28 07:54
VTHD: 0.5% / 0.8% / 0.5%
PF: 0.663
Low PF Warning
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 34053.0V / 0.0V / 34272.0V
I: 75.20A / 0.00A / 73.60A
kW: 4180.800 kW  Unbal: —
as at 2026-08-28 07:48
VTHD: 0.7% / 0.0% / 0.6%
PF: 0.808
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 34020.0V / 0.0V / 34173.0V
I: 414.40A / 9.60A / 412.80A
kW: 23654.400 kW  Unbal: —
as at 2026-08-28 07:39
VTHD: 1.0% / 0.0% / 1.0%
PF: 0.842
Low PF Warning
Ballito Sub (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 33573.0V / 0.0V / 34452.0V
I: 102.60A / 0.00A / 102.00A
kW: 5830.200 kW  Unbal: —
as at 2026-08-28 07:38
VTHD: 1.0% / 0.0% / 1.1%
PF: 0.840
Low PF Warning
Zimbali Sub (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 33957.0V / 0.0V / 33429.0V
I: 201.20A / 0.00A / 193.60A
kW: 11301.600 kW  Unbal: —
as at 2026-08-28 07:49
VTHD: 1.4% / 0.0% / 1.5%
PF: 0.851
Compliant
Site Combined Totals Mean Voltage: 20931.00 V
Total Current: 3426.6 A
Total kW: 78792.000 kW
Mean PF: 0.846 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events158891HighDLMS event log codes 210-213
Power Failures / Outages83853HighPower fail log entries
Power Cycle Events (Up/Down)107549InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%5.26%Non-Compliant
PQ Threshold Events≤ 40 / quarter158891Non-Compliant
Outages≤ 20 / quarter83853Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit