PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-08-27 17:07:02 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter158891 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter83853 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%6.36%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.5%0Compliant
3rd Harmonic (V)ReviewMax 1.4%0Compliant
5th Harmonic (V)≤ 3%Max 0.8%0Compliant
7th Harmonic (V)≤ 3%Max 0.7%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19707.0V / 20007.0V / 20049.0V
I: 205.50A / 206.00A / 206.50A
kW: 12022.500 kW  Unbal: 1.72%
as at 2026-08-27 17:03
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.973
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 19950.0V / 19869.0V / 19596.0V
I: 106.40A / 107.20A / 106.80A
kW: 6110.400 kW  Unbal: 1.79%
as at 2026-08-27 16:51
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.962
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19605.0V / 19893.0V / 19935.0V
I: 98.00A / 98.80A / 94.40A
kW: —  Unbal: 1.67%
as at 2026-08-27 16:57
VTHD: 0.6% / 0.8% / 0.6%
PF: —
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19794.0V / 19335.0V / 20601.0V
I: 284.00A / 288.00A / 275.20A
kW: 16233.600 kW  Unbal: 6.36%
as at 2026-08-27 17:02
VTHD: 0.9% / 1.5% / 1.0%
PF: 0.962
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19575.0V / 19857.0V / 19923.0V
I: 31.50A / 32.00A / 31.00A
kW: 1200.000 kW  Unbal: 1.76%
as at 2026-08-27 16:49
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.646
Low PF Warning
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19581.0V / 19866.0V / 19944.0V
I: 30.50A / 31.50A / 29.00A
kW: 1225.500 kW  Unbal: 1.83%
as at 2026-08-27 16:50
VTHD: 0.6% / 0.9% / 0.6%
PF: 0.678
Low PF Warning
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 34092.0V / 0.0V / 34179.0V
I: 129.60A / 0.00A / 123.20A
kW: 7272.000 kW  Unbal: —
as at 2026-08-27 16:52
VTHD: 0.7% / 0.0% / 0.7%
PF: 0.846
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 34632.0V / 0.0V / 34626.0V
I: 422.40A / 9.60A / 420.80A
kW: 24403.200 kW  Unbal: —
as at 2026-08-27 17:01
VTHD: 0.8% / 0.0% / 0.9%
PF: 0.836
Low PF Warning
Ballito Sub (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 33741.0V / 0.0V / 34521.0V
I: 94.20A / 0.00A / 93.00A
kW: 5418.000 kW  Unbal: —
as at 2026-08-27 16:58
VTHD: 0.9% / 0.0% / 1.0%
PF: 0.841
Low PF Warning
Zimbali Sub (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 34194.0V / 0.0V / 33606.0V
I: 232.80A / 0.00A / 222.40A
kW: 13002.000 kW  Unbal: —
as at 2026-08-27 16:52
VTHD: 1.1% / 0.0% / 1.0%
PF: 0.845
Low PF Warning
Site Combined Totals Mean Voltage: 21022.60 V
Total Current: 4010.3 A
Total kW: 86887.200 kW
Mean PF: 0.843 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events158891HighDLMS event log codes 210-213
Power Failures / Outages83853HighPower fail log entries
Power Cycle Events (Up/Down)107549InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%6.36%Non-Compliant
PQ Threshold Events≤ 40 / quarter158891Non-Compliant
Outages≤ 20 / quarter83853Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit