10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter158770 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter83835 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%5.97%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.7%0Compliant
3rd Harmonic (V)ReviewMax 1.4%0Compliant
5th Harmonic (V)≤ 3%Max 1.4%0Compliant
7th Harmonic (V)≤ 3%Max 0.8%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19626.0V / 19812.0V / 19821.0V
I: 46.00A / 47.00A / 46.00A
kW: 2739.000 kW  Unbal: 0.99%
as at 2026-07-24 02:28
VTHD: 0.5% / 0.8% / 0.6%
PF: 0.989
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 19896.0V / 19848.0V / 19677.0V
I: 34.40A / 35.60A / 35.20A
kW: 2022.000 kW  Unbal: 1.11%
as at 2026-07-24 02:27
VTHD: 0.6% / 0.8% / 0.5%
PF: 0.946
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19629.0V / 19803.0V / 19857.0V
I: 136.00A / 139.60A / 137.20A
kW: 7508.400 kW  Unbal: 1.15%
as at 2026-07-24 02:29
VTHD: 0.5% / 0.8% / 0.5%
PF: 0.923
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19740.0V / 19221.0V / 20403.0V
I: 110.40A / 112.80A / 109.60A
kW: 5800.800 kW  Unbal: 5.97%
as at 2026-07-24 02:31
VTHD: 0.8% / 1.5% / 0.9%
PF: 0.879
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19623.0V / 19818.0V / 19854.0V
I: 147.00A / 155.00A / 149.00A
kW: 8793.000 kW  Unbal: 1.17%
as at 2026-07-24 02:31
VTHD: 0.5% / 0.8% / 0.6%
PF: 0.981
Compliant
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19632.0V / 19815.0V / 19827.0V
I: 141.00A / 151.50A / 142.50A
kW: 8488.500 kW  Unbal: 0.99%
as at 2026-07-24 02:30
VTHD: 0.5% / 0.8% / 0.5%
PF: 0.977
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 33837.0V / 0.0V / 33888.0V
I: 49.60A / 0.00A / 48.00A
kW: 2601.600 kW  Unbal: —
as at 2026-07-24 02:28
VTHD: 0.6% / 0.0% / 0.6%
PF: 0.780
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 33975.0V / 0.0V / 34035.0V
I: 268.80A / 6.40A / 265.60A
kW: 15446.400 kW  Unbal: —
as at 2026-07-24 02:28
VTHD: 1.1% / 0.0% / 1.2%
PF: 0.845
Low PF Warning
Ballito Sub (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 33708.0V / 0.0V / 34218.0V
I: 54.00A / 0.00A / 54.00A
kW: 3090.600 kW  Unbal: —
as at 2026-07-24 02:30
VTHD: 1.0% / 0.0% / 1.1%
PF: 0.842
Low PF Warning
Zimbali Sub (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 34362.0V / 0.0V / 33969.0V
I: 128.00A / 0.00A / 126.80A
kW: 7440.000 kW  Unbal: —
as at 2026-07-24 02:26
VTHD: 1.7% / 0.0% / 1.7%
PF: 0.848
Low PF Warning
Site Combined Totals Mean Voltage: 20929.80 V
Total Current: 2877.0 A
Total kW: 63930.300 kW
Mean PF: 0.901 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events158770HighDLMS event log codes 210-213
Power Failures / Outages83835HighPower fail log entries
Power Cycle Events (Up/Down)107513InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%5.97%Non-Compliant
PQ Threshold Events≤ 40 / quarter158770Non-Compliant
Outages≤ 20 / quarter83835Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit