⚡ Mcor Power Quality
Kwadukuza Municipality
Logged in as Corrie Logout
MCOR Power Quality
PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-07-23 14:58:37 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter158770 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter83835 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%6.06%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.6%0Compliant
3rd Harmonic (V)ReviewMax 1.5%0Compliant
5th Harmonic (V)≤ 3%Max 0.9%0Compliant
7th Harmonic (V)≤ 3%Max 0.6%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19491.0V / 19713.0V / 19857.0V
I: 61.50A / 64.50A / 65.00A
kW: 3655.500 kW  Unbal: 1.86%
as at 2026-07-23 14:57
VTHD: 0.6% / 0.9% / 0.6%
PF: 0.982
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 19851.0V / 19704.0V / 19497.0V
I: 68.40A / 70.00A / 66.40A
kW: 3801.600 kW  Unbal: 1.80%
as at 2026-07-23 14:56
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.940
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19485.0V / 19710.0V / 19857.0V
I: 265.20A / 277.20A / 270.80A
kW: 15244.800 kW  Unbal: 1.89%
as at 2026-07-23 14:58
VTHD: 0.6% / 0.9% / 0.6%
PF: 0.952
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19479.0V / 19200.0V / 20394.0V
I: 218.40A / 224.00A / 221.60A
kW: 12429.600 kW  Unbal: 6.06%
as at 2026-07-23 14:57
VTHD: 0.7% / 1.6% / 0.9%
PF: 0.950
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19602.0V / 19800.0V / 19929.0V
I: 133.00A / 145.50A / 139.50A
kW: 8130.000 kW  Unbal: 1.65%
as at 2026-07-23 14:47
VTHD: 0.7% / 0.9% / 0.6%
PF: 0.986
Compliant
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19512.0V / 19737.0V / 19875.0V
I: 134.00A / 150.50A / 140.50A
kW: 8214.000 kW  Unbal: 1.84%
as at 2026-07-23 14:53
VTHD: 0.6% / 0.9% / 0.5%
PF: 0.977
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 33630.0V / 0.0V / 33924.0V
I: 105.60A / 0.00A / 102.40A
kW: 5894.400 kW  Unbal: —
as at 2026-07-23 14:54
VTHD: 0.8% / 0.0% / 0.6%
PF: 0.828
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 33636.0V / 0.0V / 33924.0V
I: 377.60A / 8.00A / 372.80A
kW: 21374.400 kW  Unbal: —
as at 2026-07-23 14:56
VTHD: 0.9% / 0.0% / 1.0%
PF: 0.843
Low PF Warning
Ballito Sub (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 33372.0V / 0.0V / 34137.0V
I: 91.80A / 0.00A / 91.80A
kW: 5347.800 kW  Unbal: —
as at 2026-07-23 14:48
VTHD: 1.0% / 0.0% / 1.1%
PF: 0.847
Low PF Warning
Zimbali Sub (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 33741.0V / 0.0V / 33264.0V
I: 251.60A / 0.00A / 237.60A
kW: 13898.400 kW  Unbal: —
as at 2026-07-23 14:56
VTHD: 1.0% / 0.0% / 0.9%
PF: 0.849
Low PF Warning
Site Combined Totals Mean Voltage: 20810.70 V
Total Current: 4355.2 A
Total kW: 97990.500 kW
Mean PF: 0.915 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events158770HighDLMS event log codes 210-213
Power Failures / Outages83835HighPower fail log entries
Power Cycle Events (Up/Down)107513InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%6.06%Non-Compliant
PQ Threshold Events≤ 40 / quarter158770Non-Compliant
Outages≤ 20 / quarter83835Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit