MCOR Power Quality
PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-07-22 20:19:54 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter158770 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter83835 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%5.29%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.4%0Compliant
3rd Harmonic (V)ReviewMax 1.3%0Compliant
5th Harmonic (V)≤ 3%Max 0.9%0Compliant
7th Harmonic (V)≤ 3%Max 0.9%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19716.0V / 19905.0V / 20028.0V
I: 50.00A / 52.00A / 52.00A
kW: 3009.000 kW  Unbal: 1.57%
as at 2026-07-22 20:09
VTHD: 0.6% / 0.8% / 0.5%
PF: 0.992
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 19953.0V / 19818.0V / 19560.0V
I: 54.00A / 55.20A / 53.60A
kW: 3078.000 kW  Unbal: 1.99%
as at 2026-07-22 18:07
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.954
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19740.0V / 19944.0V / 20064.0V
I: 260.80A / 272.00A / 262.00A
kW: 15290.400 kW  Unbal: 1.63%
as at 2026-07-22 20:14
VTHD: 0.6% / 0.8% / 0.5%
PF: 0.967
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19839.0V / 19407.0V / 20460.0V
I: 237.60A / 250.40A / 244.00A
kW: 13874.400 kW  Unbal: 5.29%
as at 2026-07-22 20:12
VTHD: 0.6% / 1.4% / 0.9%
PF: 0.956
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19743.0V / 19941.0V / 20055.0V
I: 144.50A / 156.50A / 150.50A
kW: 8850.000 kW  Unbal: 1.57%
as at 2026-07-22 20:14
VTHD: 0.6% / 0.8% / 0.5%
PF: 0.980
Compliant
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19728.0V / 19935.0V / 20055.0V
I: 138.00A / 152.50A / 143.50A
kW: —  Unbal: 1.64%
as at 2026-07-22 20:13
VTHD: 0.6% / 0.8% / 0.5%
PF: —
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 33543.0V / 0.0V / 33801.0V
I: 107.20A / 0.00A / 102.40A
kW: 5980.800 kW  Unbal: —
as at 2026-07-22 20:11
VTHD: 0.7% / 0.0% / 0.6%
PF: 0.845
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 34008.0V / 0.0V / 34221.0V
I: 409.60A / 9.60A / 403.20A
kW: 23313.600 kW  Unbal: —
as at 2026-07-22 20:13
VTHD: 1.0% / 0.0% / 1.1%
PF: 0.844
Low PF Warning
Ballito Sub (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 33705.0V / 0.0V / 34443.0V
I: 99.00A / 0.00A / 100.20A
kW: 5846.400 kW  Unbal: —
as at 2026-07-22 19:48
VTHD: 1.0% / 0.0% / 1.0%
PF: 0.850
Compliant
Zimbali Sub (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 34200.0V / 0.0V / 33744.0V
I: 191.60A / 0.00A / 183.20A
kW: 10842.000 kW  Unbal: —
as at 2026-07-22 20:16
VTHD: 1.2% / 0.0% / 1.2%
PF: 0.853
Compliant
Site Combined Totals Mean Voltage: 20985.20 V
Total Current: 4335.1 A
Total kW: 90084.600 kW
Mean PF: 0.916 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events158770HighDLMS event log codes 210-213
Power Failures / Outages83835HighPower fail log entries
Power Cycle Events (Up/Down)107513InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%5.29%Non-Compliant
PQ Threshold Events≤ 40 / quarter158770Non-Compliant
Outages≤ 20 / quarter83835Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit