MCOR Power Quality
PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-07-09 10:18:00 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter154761 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter83027 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%6.83%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.5%0Compliant
3rd Harmonic (V)ReviewMax 1.4%0Compliant
5th Harmonic (V)≤ 3%Max 0.9%0Compliant
7th Harmonic (V)≤ 3%Max 0.7%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19410.0V / 19668.0V / 19740.0V
I: 53.50A / 55.50A / 55.00A
kW: 3177.000 kW  Unbal: 1.68%
as at 2026-07-09 10:16
VTHD: 0.5% / 0.7% / 0.4%
PF: 0.988
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 19971.0V / 19911.0V / 19680.0V
I: 124.40A / 127.60A / 125.20A
kW: 7170.000 kW  Unbal: 1.47%
as at 2026-07-08 13:52
VTHD: 0.6% / 0.7% / 0.6%
PF: 0.946
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19410.0V / 19650.0V / 19713.0V
I: 210.80A / 218.80A / 211.60A
kW: 11954.400 kW  Unbal: 1.55%
as at 2026-07-09 10:11
VTHD: 0.5% / 0.7% / 0.4%
PF: 0.953
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19548.0V / 19131.0V / 20478.0V
I: 185.60A / 191.20A / 189.60A
kW: 10588.800 kW  Unbal: 6.83%
as at 2026-07-09 10:06
VTHD: 0.9% / 1.5% / 1.1%
PF: 0.941
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19722.0V / 19950.0V / 19944.0V
I: 85.00A / 91.00A / 87.00A
kW: 5052.000 kW  Unbal: 1.15%
as at 2026-07-09 02:25
VTHD: 0.5% / 0.7% / 0.5%
PF: 0.957
Compliant
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19458.0V / 19686.0V / 19773.0V
I: 77.50A / 86.50A / 81.00A
kW: 4600.500 kW  Unbal: 1.60%
as at 2026-07-09 10:10
VTHD: 0.6% / 0.7% / 0.5%
PF: 0.954
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 33648.0V / 0.0V / 33843.0V
I: 92.80A / 0.00A / 88.00A
kW: 5088.000 kW  Unbal: —
as at 2026-07-09 10:02
VTHD: 0.7% / 0.0% / 0.5%
PF: 0.822
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 33849.0V / 0.0V / 34011.0V
I: 396.80A / 9.60A / 387.20A
kW: 22128.000 kW  Unbal: —
as at 2026-07-09 10:12
VTHD: 0.8% / 0.0% / 0.9%
PF: 0.832
Low PF Warning
Ballito Sub Incomer (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 32379.0V / 0.0V / 33156.0V
I: 257.40A / 0.00A / 262.80A
kW: 14671.800 kW  Unbal: —
as at 2026-07-09 10:05
VTHD: 1.2% / 0.0% / 1.2%
PF: 0.856
Compliant
Zimbali Sub Incomer (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 34149.0V / 0.0V / 33570.0V
I: 243.60A / 0.00A / 232.00A
kW: 13538.400 kW  Unbal: —
as at 2026-06-25 08:34
VTHD: 1.2% / 0.0% / 1.1%
PF: 0.843
Low PF Warning
Site Combined Totals Mean Voltage: 20781.60 V
Total Current: 4227.0 A
Total kW: 97968.900 kW
Mean PF: 0.909 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events154761HighDLMS event log codes 210-213
Power Failures / Outages83027HighPower fail log entries
Power Cycle Events (Up/Down)103996InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%6.83%Non-Compliant
PQ Threshold Events≤ 40 / quarter154761Non-Compliant
Outages≤ 20 / quarter83027Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit