| Doc No: | MCOR-PQ-0001 |
| Document Ref: | MCOR-PQ-2026-Q2 |
| Period: | 2026-04-01 to 2026-06-30 |
| Generated | 2026-07-04 10:42:40 SAST |
| Parameter | NERSA Limit | Measured Range | Compliance Status |
|---|---|---|---|
| Voltage PQ Events (threshold log) | ≤ 40 events per quarter | 118060 events | Non-Compliant |
| Power Failures / Outages | ≤ 20 events per quarter | 63091 events | Non-Compliant |
| Voltage Unbalance (max site) | ≤ 2% | 7.23% | Non-Compliant |
| Flicker Pst (short-term, max site) | ≤ 1.0 | 0.00 | Compliant |
| Flicker Plt (long-term, max site) | ≤ 0.8 | 0.00 | Compliant |
| Parameter | NERSA Limit | Measured Max (all meters) | Phases Exceeding Limit | Compliance Status |
|---|---|---|---|---|
| THD Voltage (VTHD) | ≤ 5% | Max 1.5% | 0 | Compliant |
| 3rd Harmonic (V) | Review | Max 1.5% | 0 | Compliant |
| 5th Harmonic (V) | ≤ 3% | Max 0.8% | 0 | Compliant |
| 7th Harmonic (V) | ≤ 3% | Max 0.7% | 0 | Compliant |
| Meter / Feeder | Voltage / Current / kW Snapshot | VTHD & PF | Compliance Status |
|---|---|---|---|
| Stanger-Feeder 1 (33KV) / Feeder 1 Stanger Substation |
V: 19623.0V / 19797.0V / 19866.0V I: 42.00A / 42.00A / 42.00A kW: 2439.000 kW Unbal: 1.23% as at 2026-07-04 10:30 |
VTHD: 0.3% / 0.8% / 0.4% PF: 0.986 |
Compliant |
| Stanger-Feeder 2 (33kV) / Feeder 2 Stanger Substation |
V: 19875.0V / 19800.0V / 19626.0V I: 101.20A / 101.60A / 101.60A kW: 5844.000 kW Unbal: 1.26% as at 2026-07-04 10:30 |
VTHD: 0.5% / 0.7% / 0.4% PF: 0.962 |
Compliant |
| Stanger-Gelnhills Feed (33KV) / Feeder 3 Stanger Substation |
V: 19677.0V / 19746.0V / 19851.0V I: 203.20A / 204.00A / 206.40A kW: 11730.000 kW Unbal: 0.88% as at 2026-07-04 10:24 |
VTHD: 0.3% / 0.8% / 0.4% PF: 0.962 |
Compliant |
| Stanger-Groutville Phase1 (33KV) / Feeder 4 Stanger Substation |
V: 19695.0V / 19182.0V / 20616.0V I: 202.40A / 204.80A / 199.20A kW: 11354.400 kW Unbal: 7.23% as at 2026-07-04 10:34 |
VTHD: 1.1% / 1.5% / 1.0% PF: 0.946 |
Compliant |
| Stanger-Sappi Feed 1 (33KV) / Feeder 5 Stanger Substation |
V: 19677.0V / 19779.0V / 19929.0V I: 88.50A / 94.50A / 94.50A kW: 5094.000 kW Unbal: 1.27% as at 2026-07-04 10:25 |
VTHD: 0.4% / 0.7% / 0.5% PF: 0.951 |
Compliant |
| Stanger-Sappi Feed 2 (33KV) / Feeder 6 Stanger Substation |
V: 19743.0V / 19860.0V / 19917.0V I: 84.00A / 89.50A / 86.50A kW: 4965.000 kW Unbal: 0.88% as at 2026-07-04 10:39 |
VTHD: 0.4% / 0.7% / 0.4% PF: 0.945 |
Compliant |
| Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7 Shakaskraal Substation |
V: 34248.0V / 0.0V / 34437.0V I: 91.20A / 0.00A / 88.00A kW: 5112.000 kW Unbal: — as at 2026-07-04 10:26 |
VTHD: 0.7% / 0.0% / 0.5% PF: 0.825 |
Low PF Warning |
| Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8 Shakaskraal Substation |
V: 34251.0V / 0.0V / 34323.0V I: 356.80A / 8.00A / 352.00A kW: 20620.800 kW Unbal: — as at 2026-07-04 10:30 |
VTHD: 0.7% / 0.0% / 0.8% PF: 0.837 |
Low PF Warning |
| Ballito Sub Incomer (Feeder 1) (33KV) / Feeder 9 Driefontein Substation's |
V: 32529.0V / 0.0V / 33318.0V I: 315.00A / 0.00A / 322.80A kW: 18000.000 kW Unbal: — as at 2026-07-04 10:08 |
VTHD: 1.1% / 0.0% / 1.1% PF: 0.857 |
Compliant |
| Zimbali Sub Incomer (Feeder 2) (33KV) / Feeder 10 Driefontein Substation's |
V: 34149.0V / 0.0V / 33570.0V I: 243.60A / 0.00A / 232.00A kW: 13538.400 kW Unbal: — as at 2026-06-25 08:34 |
VTHD: 1.2% / 0.0% / 1.1% PF: 0.843 |
Low PF Warning |
| Site Combined Totals |
Mean Voltage: 20902.80 V Total Current: 4197.3 A Total kW: 98697.600 kW |
Mean PF: 0.911 | Live |
| Event Type | Count | Severity | Notes |
|---|---|---|---|
| Voltage PQ Threshold Events | 118060 | High | DLMS event log codes 210-213 |
| Power Failures / Outages | 63091 | High | Power fail log entries |
| Power Cycle Events (Up/Down) | 77673 | Investigate | Standard event codes 1 & 2 |
| Harmonic Exceedances (V H5/H7) | 0 | Low | All within limit |
| Metric | Target | Actual | Status |
|---|---|---|---|
| Meters Compliant (VTHD) | ≥ 95% | 100.0% | Compliant |
| Voltage Unbalance | ≤ 2% | 7.23% | Non-Compliant |
| PQ Threshold Events | ≤ 40 / quarter | 118060 | Non-Compliant |
| Outages | ≤ 20 / quarter | 63091 | Non-Compliant |
| Harmonic Incidents (H5/H7) | ≤ 10 | 0 | Within Limit |