MCOR Power Quality
PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-07-04 10:42:40 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter118060 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter63091 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%7.23%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.5%0Compliant
3rd Harmonic (V)ReviewMax 1.5%0Compliant
5th Harmonic (V)≤ 3%Max 0.8%0Compliant
7th Harmonic (V)≤ 3%Max 0.7%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19623.0V / 19797.0V / 19866.0V
I: 42.00A / 42.00A / 42.00A
kW: 2439.000 kW  Unbal: 1.23%
as at 2026-07-04 10:30
VTHD: 0.3% / 0.8% / 0.4%
PF: 0.986
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 19875.0V / 19800.0V / 19626.0V
I: 101.20A / 101.60A / 101.60A
kW: 5844.000 kW  Unbal: 1.26%
as at 2026-07-04 10:30
VTHD: 0.5% / 0.7% / 0.4%
PF: 0.962
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19677.0V / 19746.0V / 19851.0V
I: 203.20A / 204.00A / 206.40A
kW: 11730.000 kW  Unbal: 0.88%
as at 2026-07-04 10:24
VTHD: 0.3% / 0.8% / 0.4%
PF: 0.962
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19695.0V / 19182.0V / 20616.0V
I: 202.40A / 204.80A / 199.20A
kW: 11354.400 kW  Unbal: 7.23%
as at 2026-07-04 10:34
VTHD: 1.1% / 1.5% / 1.0%
PF: 0.946
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19677.0V / 19779.0V / 19929.0V
I: 88.50A / 94.50A / 94.50A
kW: 5094.000 kW  Unbal: 1.27%
as at 2026-07-04 10:25
VTHD: 0.4% / 0.7% / 0.5%
PF: 0.951
Compliant
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19743.0V / 19860.0V / 19917.0V
I: 84.00A / 89.50A / 86.50A
kW: 4965.000 kW  Unbal: 0.88%
as at 2026-07-04 10:39
VTHD: 0.4% / 0.7% / 0.4%
PF: 0.945
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 34248.0V / 0.0V / 34437.0V
I: 91.20A / 0.00A / 88.00A
kW: 5112.000 kW  Unbal: —
as at 2026-07-04 10:26
VTHD: 0.7% / 0.0% / 0.5%
PF: 0.825
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 34251.0V / 0.0V / 34323.0V
I: 356.80A / 8.00A / 352.00A
kW: 20620.800 kW  Unbal: —
as at 2026-07-04 10:30
VTHD: 0.7% / 0.0% / 0.8%
PF: 0.837
Low PF Warning
Ballito Sub Incomer (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 32529.0V / 0.0V / 33318.0V
I: 315.00A / 0.00A / 322.80A
kW: 18000.000 kW  Unbal: —
as at 2026-07-04 10:08
VTHD: 1.1% / 0.0% / 1.1%
PF: 0.857
Compliant
Zimbali Sub Incomer (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 34149.0V / 0.0V / 33570.0V
I: 243.60A / 0.00A / 232.00A
kW: 13538.400 kW  Unbal: —
as at 2026-06-25 08:34
VTHD: 1.2% / 0.0% / 1.1%
PF: 0.843
Low PF Warning
Site Combined Totals Mean Voltage: 20902.80 V
Total Current: 4197.3 A
Total kW: 98697.600 kW
Mean PF: 0.911 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events118060HighDLMS event log codes 210-213
Power Failures / Outages63091HighPower fail log entries
Power Cycle Events (Up/Down)77673InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%7.23%Non-Compliant
PQ Threshold Events≤ 40 / quarter118060Non-Compliant
Outages≤ 20 / quarter63091Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit