⚡ Mcor Power Quality Portal
Kwadukuza Municipality
Logged in as Corrie Logout
← Back to Combined Hub ⬇ Export Excel
MCOR Power Quality
PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-06-26 11:40:06 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter37357 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter20834 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%7.28%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.5%0Compliant
3rd Harmonic (V)ReviewMax 1.3%0Compliant
5th Harmonic (V)≤ 3%Max 0.8%0Compliant
7th Harmonic (V)≤ 3%Max 0.7%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19665.0V / 19902.0V / 19971.0V
I: 52.50A / 54.50A / 52.50A
kW: 3198.000 kW  Unbal: 1.54%
as at 2026-06-26 11:27
VTHD: 0.5% / 0.8% / 0.5%
PF: 0.988
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 20007.0V / 19848.0V / 19677.0V
I: 103.60A / 105.20A / 103.20A
kW: 5913.600 kW  Unbal: 1.66%
as at 2026-06-26 11:33
VTHD: 0.6% / 0.8% / 0.5%
PF: 0.955
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19644.0V / 19884.0V / 19953.0V
I: 196.00A / 201.20A / 196.80A
kW: 10958.400 kW  Unbal: 1.56%
as at 2026-06-26 11:24
VTHD: 0.5% / 0.8% / 0.5%
PF: 0.942
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19473.0V / 19023.0V / 20454.0V
I: 218.40A / 227.20A / 222.40A
kW: 12254.400 kW  Unbal: 7.28%
as at 2026-06-26 11:39
VTHD: 0.8% / 1.5% / 1.1%
PF: 0.927
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19695.0V / 19911.0V / 19959.0V
I: 107.00A / 118.00A / 112.50A
kW: 6712.500 kW  Unbal: 1.33%
as at 2026-06-26 11:24
VTHD: 0.5% / 0.8% / 0.5%
PF: 0.996
Compliant
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19680.0V / 19884.0V / 19971.0V
I: 115.00A / 120.50A / 111.00A
kW: 6885.000 kW  Unbal: 1.47%
as at 2026-06-26 11:26
VTHD: 0.5% / 0.8% / 0.5%
PF: 0.997
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 33591.0V / 0.0V / 33798.0V
I: 99.20A / 0.00A / 94.40A
kW: 5577.600 kW  Unbal: —
as at 2026-06-26 06:12
VTHD: 0.7% / 0.0% / 0.5%
PF: 0.842
Low PF Warning
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 34215.0V / 0.0V / 34362.0V
I: 371.20A / 8.00A / 366.40A
kW: 20937.600 kW  Unbal: —
as at 2026-06-26 11:35
VTHD: 0.8% / 0.0% / 0.8%
PF: 0.812
Low PF Warning
Ballito Sub Incomer (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 32505.0V / 0.0V / 33291.0V
I: 306.60A / 0.00A / 315.00A
kW: 17535.600 kW  Unbal: —
as at 2026-06-26 11:31
VTHD: 1.1% / 0.0% / 1.2%
PF: 0.856
Compliant
Zimbali Sub Incomer (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 34149.0V / 0.0V / 33570.0V
I: 243.60A / 0.00A / 232.00A
kW: 13538.400 kW  Unbal: —
as at 2026-06-25 08:34
VTHD: 1.2% / 0.0% / 1.1%
PF: 0.843
Low PF Warning
Site Combined Totals Mean Voltage: 20869.40 V
Total Current: 4453.9 A
Total kW: 103511.100 kW
Mean PF: 0.916 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events37357HighDLMS event log codes 210-213
Power Failures / Outages20834HighPower fail log entries
Power Cycle Events (Up/Down)33728InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%7.28%Non-Compliant
PQ Threshold Events≤ 40 / quarter37357Non-Compliant
Outages≤ 20 / quarter20834Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit