MCOR Power Quality
PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-06-23 18:15:18 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter437 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter98 eventsNon-Compliant
Voltage Unbalance (max site)≤ 2%7.27%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.4%0Compliant
3rd Harmonic (V)ReviewMax 1.4%0Compliant
5th Harmonic (V)≤ 3%Max 0.6%0Compliant
7th Harmonic (V)≤ 3%Max 0.8%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19647.0V / 19980.0V / 20058.0V
I: 44.00A / 45.50A / 43.50A
kW: 2610.000 kW  Unbal: 2.07%
as at 2026-06-23 18:05
VTHD: 0.5% / 0.7% / 0.4%
PF: 0.993
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 20073.0V / 19971.0V / 19641.0V
I: 100.80A / 104.00A / 102.80A
kW: 6018.000 kW  Unbal: 2.17%
as at 2026-06-23 18:14
VTHD: 0.4% / 0.7% / 0.5%
PF: 0.975
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19668.0V / 20013.0V / 20064.0V
I: 322.00A / 324.80A / 322.00A
kW: 18907.200 kW  Unbal: 1.99%
as at 2026-06-23 18:08
VTHD: 0.5% / 0.7% / 0.4%
PF: 0.976
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19770.0V / 19224.0V / 20670.0V
I: 0.00A / 0.00A / 0.00A
kW: 0.000 kW  Unbal: 7.27%
as at 2026-06-23 18:05
VTHD: 0.7% / 1.4% / 0.9%
PF: -0.030
Low PF Warning
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19635.0V / 19974.0V / 20052.0V
I: 132.00A / 153.00A / 142.50A
kW: 8401.500 kW  Unbal: 2.10%
as at 2026-06-23 18:15
VTHD: 0.6% / 0.8% / 0.6%
PF: 0.981
Compliant
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19653.0V / 19995.0V / 20058.0V
I: 137.50A / 148.50A / 133.50A
kW: 8317.500 kW  Unbal: 2.03%
as at 2026-06-23 18:06
VTHD: 0.5% / 0.7% / 0.4%
PF: 0.982
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 34242.0V / 0.0V / 34410.0V
I: 171.20A / 0.00A / 155.20A
kW: 9528.000 kW  Unbal: —
as at 2026-06-23 18:09
VTHD: 0.6% / 0.0% / 0.5%
PF: 0.850
Compliant
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 34602.0V / 0.0V / 34716.0V
I: 504.00A / 11.20A / 489.60A
kW: 29112.000 kW  Unbal: —
as at 2026-06-23 18:15
VTHD: 0.7% / 0.0% / 0.7%
PF: 0.840
Low PF Warning
Ballito Sub Incomer (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 33741.0V / 0.0V / 34704.0V
I: 109.20A / 0.00A / 109.20A
kW: 6377.400 kW  Unbal: —
as at 2026-06-23 18:07
VTHD: 0.8% / 0.0% / 0.7%
PF: 0.846
Low PF Warning
Zimbali Sub Incomer (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 34482.0V / 0.0V / 33786.0V
I: 249.60A / 0.00A / 236.00A
kW: 14138.400 kW  Unbal: —
as at 2026-06-23 18:10
VTHD: 1.2% / 0.0% / 1.0%
PF: 0.846
Low PF Warning
Site Combined Totals Mean Voltage: 21094.30 V
Total Current: 4291.6 A
Total kW: 103410.000 kW
Mean PF: 0.826 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events437HighDLMS event log codes 210-213
Power Failures / Outages98HighPower fail log entries
Power Cycle Events (Up/Down)324InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%7.27%Non-Compliant
PQ Threshold Events≤ 40 / quarter437Non-Compliant
Outages≤ 20 / quarter98Non-Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit