MCOR Power Quality
PQ Mon ReportQ2 2026
Doc No:MCOR-PQ-0001
Document Ref:MCOR-PQ-2026-Q2
Period:2026-04-01 to 2026-06-30
Generated2026-06-22 19:11:16 SAST

10.3   Voltage Compliance

ParameterNERSA LimitMeasured RangeCompliance Status
Voltage PQ Events (threshold log)≤ 40 events per quarter163 eventsNon-Compliant
Power Failures / Outages≤ 20 events per quarter0 eventsCompliant
Voltage Unbalance (max site)≤ 2%7.12%Non-Compliant
Flicker Pst (short-term, max site)≤ 1.00.00Compliant
Flicker Plt (long-term, max site)≤ 0.80.00Compliant

10.4   Harmonic Distortion

ParameterNERSA LimitMeasured Max (all meters)Phases Exceeding LimitCompliance Status
THD Voltage (VTHD)≤ 5%Max 1.4%0Compliant
3rd Harmonic (V)ReviewMax 1.3%0Compliant
5th Harmonic (V)≤ 3%Max 0.8%0Compliant
7th Harmonic (V)≤ 3%Max 0.9%0Compliant

10.5   Feeder Loading & Power Factor

Meter / FeederVoltage / Current / kW SnapshotVTHD & PFCompliance Status
Stanger-Feeder 1 (33KV) / Feeder 1
Stanger Substation
V: 19773.0V / 20031.0V / 20115.0V
I: 42.00A / 43.00A / 41.00A
kW: 2683.500 kW  Unbal: 1.71%
as at 2026-06-22 19:06
VTHD: 0.5% / 0.7% / 0.4%
PF: 0.987
Compliant
Stanger-Feeder 2 (33kV) / Feeder 2
Stanger Substation
V: 20166.0V / 20049.0V / 19827.0V
I: 101.60A / 104.40A / 102.40A
kW: 5974.800 kW  Unbal: 1.69%
as at 2026-06-22 19:10
VTHD: 0.4% / 0.7% / 0.5%
PF: 0.973
Compliant
Stanger-Gelnhills Feed (33KV) / Feeder 3
Stanger Substation
V: 19779.0V / 19998.0V / 20094.0V
I: 277.20A / 276.00A / 274.40A
kW: 15974.400 kW  Unbal: 1.58%
as at 2026-06-22 19:11
VTHD: 0.5% / 0.7% / 0.4%
PF: 0.975
Compliant
Stanger-Groutville Phase1 (33KV) / Feeder 4
Stanger Substation
V: 19893.0V / 19317.0V / 20739.0V
I: 303.20A / 312.00A / 302.40A
kW: 17736.000 kW  Unbal: 7.12%
as at 2026-06-22 19:01
VTHD: 0.7% / 1.4% / 1.0%
PF: 0.965
Compliant
Stanger-Sappi Feed 1 (33KV) / Feeder 5
Stanger Substation
V: 19764.0V / 20007.0V / 20112.0V
I: 132.00A / 150.50A / 144.00A
kW: 8527.500 kW  Unbal: 1.74%
as at 2026-06-22 19:05
VTHD: 0.5% / 0.7% / 0.4%
PF: 0.985
Compliant
Stanger-Sappi Feed 2 (33KV) / Feeder 6
Stanger Substation
V: 19800.0V / 20052.0V / 20115.0V
I: 144.50A / 152.50A / 140.50A
kW: 8629.500 kW  Unbal: 1.58%
as at 2026-06-22 19:09
VTHD: 0.5% / 0.7% / 0.4%
PF: 0.982
Compliant
Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7
Shakaskraal Substation
V: 34083.0V / 0.0V / 34392.0V
I: 145.60A / 0.00A / 132.80A
kW: 8121.600 kW  Unbal: —
as at 2026-06-22 19:05
VTHD: 0.5% / 0.0% / 0.5%
PF: 0.856
Compliant
Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8
Shakaskraal Substation
V: 34590.0V / 0.0V / 34785.0V
I: 460.80A / 9.60A / 444.80A
kW: 27134.400 kW  Unbal: —
as at 2026-06-22 19:03
VTHD: 0.8% / 0.0% / 1.0%
PF: 0.850
Compliant
Ballito Sub Incomer (Feeder 1) (33KV) / Feeder 9
Driefontein Substation's
V: 33777.0V / 0.0V / 34635.0V
I: 98.40A / 0.00A / 97.80A
kW: 5652.000 kW  Unbal: —
as at 2026-06-22 19:05
VTHD: 0.8% / 0.0% / 0.7%
PF: 0.847
Low PF Warning
Zimbali Sub Incomer (Feeder 2) (33KV) / Feeder 10
Driefontein Substation's
V: 34392.0V / 0.0V / 33861.0V
I: 219.20A / 0.00A / 202.80A
kW: 12106.800 kW  Unbal: —
as at 2026-06-22 19:06
VTHD: 1.2% / 0.0% / 1.2%
PF: 0.846
Low PF Warning
Site Combined Totals Mean Voltage: 21138.20 V
Total Current: 4855.4 A
Total kW: 112540.500 kW
Mean PF: 0.927 Live

10.6   PQ Event Summary (2026-04-01 to 2026-06-30)

Event TypeCountSeverityNotes
Voltage PQ Threshold Events163HighDLMS event log codes 210-213
Power Failures / Outages0LowPower fail log entries
Power Cycle Events (Up/Down)132InvestigateStandard event codes 1 & 2
Harmonic Exceedances (V H5/H7)0LowAll within limit

10.7   Compliance Summary

MetricTargetActualStatus
Meters Compliant (VTHD)≥ 95%100.0%Compliant
Voltage Unbalance≤ 2%7.12%Non-Compliant
PQ Threshold Events≤ 40 / quarter163Non-Compliant
Outages≤ 20 / quarter0Compliant
Harmonic Incidents (H5/H7)≤ 100Within Limit