| Doc No: | MCOR-PQ-0001 |
| Document Ref: | MCOR-PQ-2026-Q2 |
| Period: | 2026-04-01 to 2026-06-30 |
| Generated | 2026-06-22 19:11:16 SAST |
| Parameter | NERSA Limit | Measured Range | Compliance Status |
|---|---|---|---|
| Voltage PQ Events (threshold log) | ≤ 40 events per quarter | 163 events | Non-Compliant |
| Power Failures / Outages | ≤ 20 events per quarter | 0 events | Compliant |
| Voltage Unbalance (max site) | ≤ 2% | 7.12% | Non-Compliant |
| Flicker Pst (short-term, max site) | ≤ 1.0 | 0.00 | Compliant |
| Flicker Plt (long-term, max site) | ≤ 0.8 | 0.00 | Compliant |
| Parameter | NERSA Limit | Measured Max (all meters) | Phases Exceeding Limit | Compliance Status |
|---|---|---|---|---|
| THD Voltage (VTHD) | ≤ 5% | Max 1.4% | 0 | Compliant |
| 3rd Harmonic (V) | Review | Max 1.3% | 0 | Compliant |
| 5th Harmonic (V) | ≤ 3% | Max 0.8% | 0 | Compliant |
| 7th Harmonic (V) | ≤ 3% | Max 0.9% | 0 | Compliant |
| Meter / Feeder | Voltage / Current / kW Snapshot | VTHD & PF | Compliance Status |
|---|---|---|---|
| Stanger-Feeder 1 (33KV) / Feeder 1 Stanger Substation |
V: 19773.0V / 20031.0V / 20115.0V I: 42.00A / 43.00A / 41.00A kW: 2683.500 kW Unbal: 1.71% as at 2026-06-22 19:06 |
VTHD: 0.5% / 0.7% / 0.4% PF: 0.987 |
Compliant |
| Stanger-Feeder 2 (33kV) / Feeder 2 Stanger Substation |
V: 20166.0V / 20049.0V / 19827.0V I: 101.60A / 104.40A / 102.40A kW: 5974.800 kW Unbal: 1.69% as at 2026-06-22 19:10 |
VTHD: 0.4% / 0.7% / 0.5% PF: 0.973 |
Compliant |
| Stanger-Gelnhills Feed (33KV) / Feeder 3 Stanger Substation |
V: 19779.0V / 19998.0V / 20094.0V I: 277.20A / 276.00A / 274.40A kW: 15974.400 kW Unbal: 1.58% as at 2026-06-22 19:11 |
VTHD: 0.5% / 0.7% / 0.4% PF: 0.975 |
Compliant |
| Stanger-Groutville Phase1 (33KV) / Feeder 4 Stanger Substation |
V: 19893.0V / 19317.0V / 20739.0V I: 303.20A / 312.00A / 302.40A kW: 17736.000 kW Unbal: 7.12% as at 2026-06-22 19:01 |
VTHD: 0.7% / 1.4% / 1.0% PF: 0.965 |
Compliant |
| Stanger-Sappi Feed 1 (33KV) / Feeder 5 Stanger Substation |
V: 19764.0V / 20007.0V / 20112.0V I: 132.00A / 150.50A / 144.00A kW: 8527.500 kW Unbal: 1.74% as at 2026-06-22 19:05 |
VTHD: 0.5% / 0.7% / 0.4% PF: 0.985 |
Compliant |
| Stanger-Sappi Feed 2 (33KV) / Feeder 6 Stanger Substation |
V: 19800.0V / 20052.0V / 20115.0V I: 144.50A / 152.50A / 140.50A kW: 8629.500 kW Unbal: 1.58% as at 2026-06-22 19:09 |
VTHD: 0.5% / 0.7% / 0.4% PF: 0.982 |
Compliant |
| Shakaskraal-Feeder 1 (North) (33KV) / Feeder 7 Shakaskraal Substation |
V: 34083.0V / 0.0V / 34392.0V I: 145.60A / 0.00A / 132.80A kW: 8121.600 kW Unbal: — as at 2026-06-22 19:05 |
VTHD: 0.5% / 0.0% / 0.5% PF: 0.856 |
Compliant |
| Shakaskraal-Feeder 2 (South) (33KV) / Feeder 8 Shakaskraal Substation |
V: 34590.0V / 0.0V / 34785.0V I: 460.80A / 9.60A / 444.80A kW: 27134.400 kW Unbal: — as at 2026-06-22 19:03 |
VTHD: 0.8% / 0.0% / 1.0% PF: 0.850 |
Compliant |
| Ballito Sub Incomer (Feeder 1) (33KV) / Feeder 9 Driefontein Substation's |
V: 33777.0V / 0.0V / 34635.0V I: 98.40A / 0.00A / 97.80A kW: 5652.000 kW Unbal: — as at 2026-06-22 19:05 |
VTHD: 0.8% / 0.0% / 0.7% PF: 0.847 |
Low PF Warning |
| Zimbali Sub Incomer (Feeder 2) (33KV) / Feeder 10 Driefontein Substation's |
V: 34392.0V / 0.0V / 33861.0V I: 219.20A / 0.00A / 202.80A kW: 12106.800 kW Unbal: — as at 2026-06-22 19:06 |
VTHD: 1.2% / 0.0% / 1.2% PF: 0.846 |
Low PF Warning |
| Site Combined Totals |
Mean Voltage: 21138.20 V Total Current: 4855.4 A Total kW: 112540.500 kW |
Mean PF: 0.927 | Live |
| Event Type | Count | Severity | Notes |
|---|---|---|---|
| Voltage PQ Threshold Events | 163 | High | DLMS event log codes 210-213 |
| Power Failures / Outages | 0 | Low | Power fail log entries |
| Power Cycle Events (Up/Down) | 132 | Investigate | Standard event codes 1 & 2 |
| Harmonic Exceedances (V H5/H7) | 0 | Low | All within limit |
| Metric | Target | Actual | Status |
|---|---|---|---|
| Meters Compliant (VTHD) | ≥ 95% | 100.0% | Compliant |
| Voltage Unbalance | ≤ 2% | 7.12% | Non-Compliant |
| PQ Threshold Events | ≤ 40 / quarter | 163 | Non-Compliant |
| Outages | ≤ 20 / quarter | 0 | Compliant |
| Harmonic Incidents (H5/H7) | ≤ 10 | 0 | Within Limit |